Reading Gas Pressure; Furnace Control Board - Johnson Controls TG9S*MP Installation Manual

Residential gas furnace 95.5% afue single stage multi-position
Hide thumbs Also See for TG9S*MP:
Table of Contents

Advertisement

MANIFOLD PRESSURE "U" TUBE CONNECTION
OUTLET
PRESSURE TAP
GAS VALVE
FLAME
SENSOR
GAS
BURNERS
FIGURE 42: Reading Gas Pressure
ADJUSTMENT OF TEMPERATURE RISE
DANGER
The temperature rise, or temperature difference between the return
air and the supply (heated) air from the furnace, must be within the
range shown on the furnace rating plate and within the application
limitations shown in Table 6.
The supply air temperature cannot exceed the "Maximum Supply
Air Temperature" specified in these instructions and on the furnace
rating plate. Under NO circumstances can the furnace be allowed to
operate above the Maximum Supply Air Temperature. Operating the
furnace above the Maximum Supply Air Temperature will cause pre-
mature heat exchanger failure, high levels of Carbon Monoxide, a fire
hazard, personal injury, property damage, and/or death.
Blower Off Delay Timer
Adjustment Jumper
(in seconds)
FIGURE 43: Furnace Control Board
Johnson Controls Unitary Products
1/4" TUBING
MAINIFOLD
PIPE
3.5 IN
WATER
COLUMN
GAS
PRESSURE
U-TUBE
SHOWN
MANOMETER
TWIN
After about 5 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts,
about six feet (1.8 m) from the furnace where they will not be affected
by radiant heat. Increase the blower speed to decrease the temperature
rise; decrease the blower speed to increase the rise.
All direct-drive blowers have multi-speed motors. The blower motor
speed taps are located on the furnace control board in the blower com-
partment. Refer to Figure 42, and the unit-wiring label to change the
blower speed. To use the same speed tap for heating and cooling, the
heat terminal and cool terminal must be connected using a jumper wire
and connected to the desired motor lead. Place all unused motor leads
on Park terminals. Two park terminals are provided.
Do not energize more than one motor speed at a time or damage to
the motor will result.
ADJUSTMENT OF FAN CONTROL SETTINGS
This furnace is equipped with a time-on/time-off heating fan control. The
fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,
90, 120 and 180 seconds). The fan off delay is factory set to 120 sec-
onds. The fan-off setting must be long enough to adequately cool the
furnace, but not so long that cold air is blown into the heated space. The
fan-off timing may be adjusted by positioning the jumper on two of the
four pins as shown in Figure 42.
PARK PARK
HUM
364861-UIM-H-0712