Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser's purposes, the matter should be referred to the local Toshiba sales office. The contents of this instruction manual shall not become a part of or modify any prior or existing agreement, commitment, or relationship.
TOSHIBA GENERAL SAFETY INSTRUCTIONS Warnings in this manual appear in two different ways: Danger warnings - The danger warning symbol is an exclamation mark enclosed in a triangle that precedes the large bold letters spelling the word "DANGER". The Danger warning symbol is used to indicate...
The maximum ambient temperature in which this UPS unit should be operated or stored is 104 °F (40 °C). The batteries for the Toshiba 1700 Series 1.5 and 2.4kVA UPS are housed in a self-contained battery module. This module should not be opened under any circumstances.
Page 7
TOSHIBA INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ CONSERVER CES INSTRUCTIONS. Cette notice contient des instructions importantes concernant la sécurit. Une batterie peut présenter un risque de ATTENTION choc électrique, de brûlure par transfert d’énergie. Pour le remplacement, utiliser le même ATTENTION nombre de batteries du modèle suivant.
TOSHIBA Inspection/Installation Inspection of the New UPS Equipment Upon receipt of the UPS, a careful inspection for shipping damage should be made. After Unpacking: 1) Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipment, keep all original packing materials for return to shipping agent.
(unless appropriate sizing is done by a Toshiba applications engineer, or other qualified personnel). 5) Do not insert metal objects or combustible materials in the unit's ventilation slots.
TOSHIBA Battery Module Figure 2 Battery Module Layout UPS Connections Standard Module Connections The illustration on the following page shows the proper assembly of the two modules that make up the standard unit. If additional battery modules are being installed with the standard unit see page 20. For all other option modules see page 21.
Page 11
TOSHIBA Standard Module Connections (cont’d) If two modules are to be stacked on top of each other, they should be interlocked to reduce the chances of the top module being knocked over. Modules do not have to be stacked for the system to operate.
TOSHIBA Operating the UPS Display Panel Layout Function Startup on Control Battery Button Button ON LINE (green lamp) Lights green when the UPS’s inverter is supplying power to the load. AC INPUT (green lamp) Lights green when normal AC input power is being supplied to the UPS unit.
TOSHIBA Starting on DC Power If no AC power source is available, the UPS can be started from battery power. The length of UPS operation time on battery power depends on the number of attached battery modules and the amount of load the UPS is supporting.
Only one additional battery module may be added to the standard unit. For longer runtime options contact your Toshiba sales representative or the Toshiba marketing department at (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com. Table 1...
TOSHIBA Table 2 Battery Recharge Time* Unit Standard Unit With Expansion Battery Module 1500 VA 3 ½ hours 7 hours 2000 VA 3 ½ hours 7 hours 2400 VA 3 ½ hours 7 hours * Recharge times are to 90% full capacity.
Page 18
TOSHIBA press and hold the Function Control button until the battery LED begins flashing. The self-test performs the same battery check described above. 2) Alarm Silence. The alarm silence feature is used to stop the audible alarm from sounding. Any time the audible alarm is sounding pressing the Function Control button will silence the alarm.
Page 19
TOSHIBA return the system to normal operation switch the RUN/STOP switch back to the RUN position. B. Bypass Enable/Disable. Press the function control button. The unit is now ready to change the bypass enable/disable option. This is indicated by the backup LED turning off and the 150% LED turning on.
For instructions on setting the output frequency through software please contact Toshiba at (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com. It is important to note that when the UPS is operating with a fixed output frequency, output is disabled in bypass.
There are a number of other optional modules that can be ordered for the 1700 Series UPS system. Table 3 shows the available option modules. For information about options not listed here contact Toshiba’s UPS Marketing Department at (800) 231-1412 or by e-mail at toshibaups@tic.toshiba.com. Table 3...
For those cases where the unit does not transfer back automatically use the "System Reset" procedure to transfer the UPS back to normal mode (see “System Reset”, page 16). If the system faults again after being reset contact your Toshiba UPS service representative at 1-800-231-1412.
It is illegal to dump lead-acid batteries in landfills or dispose of improperly. Please help our Earth by contacting the environmental protection agencies in your area, the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for more information about recycling.
Schedule authorized Toshiba service centers to perform internal parts inspections annually, or call a Toshiba UPS service representative at 1-800-231-1412. Proper maintenance of the battery system...
TOSHIBA Appendix A: Specifications Model Number UF1A1A015C6(T) UF1A1A024C6(T) Capacity 1500VA (1.05KW) 2400VA (1.68KW) Input voltage Single phase 120VAC, +20% to -50% Input frequency 45 to 65 Hz Input Input capacity 1500VA 2400VA Input power factor Approximately unity (0.95 to 1.0) Input voltage Single phase 120VAC, ±10%...
TOSHIBA Appendix B: Fan Speed Control The fans in the 1700 Series will operate at any of four different speeds depending on the environment and system conditions. In the first stage the fans are off. As the load and or the ambient temperature increase the fans will subsequently go to low, medium or high speed as required.
TOSHIBA Appendix C: System Overload Rating The 1700 Series UPS is capable of supporting short duration overloads. When operating in the On Line mode output overloading of 125% of the rated output current can be supported for 1 minute, and 150% for 30 seconds.
TOSHIBA Appendix D: Parallel Operation The 1700 Series UPS offers a standard feature that allows the unit to operate with very low input voltage without de-rating the output power. If the input voltage drops below a certain point the unit will switch to parallel mode.
TOSHIBA Appendix E: Bypass Undervoltage / Overvoltage When the 1700 Series UPS is in bypass mode and bypass is disabled the undervoltage and overvoltage limits are restricted to +/-10% of the rated input voltage. If the input voltage is outside of this voltage window the UPS output will be turned off.
TOSHIBA Appendix F: Unit Configuration Options The following chart shows the configuration options for each base model UPS. Available Option Model Number Description Modules Description 48V battery module UF1-BC-087 Extended runtime 48V battery UF1-EBC-087 module 1500VA 208V input; 240V/120V output...
For the 1700 Series the warranty applies if the unit is sent and returned (paid for) by the user to/from the Toshiba plant or a Toshiba designated Authorized Service Center. If any UPS, part of UPS, and/or BATTERY fails to conform or is defective then TIC will repair or replace it at TIC’s option.
Page 39
TOSHIBA PROCEDURE User must contact TIC via e-mail upsservice@tic.toshiba.com, or phone 1-800-231-1412, no later than 90 days after User’s discovery of occurrence or defect in UPS, UPS part, and/or BATTERY but in no event after the expiration of the respective warranty period.