Gas Supply Pressure Measurement - Goodman MH95 Installation Instructions Manual

Gas-fired warm air furnace
Table of Contents

Advertisement

NOTE: This furnace is equipped with an ignition device which
automatically lights the burner. Do not try to light the burner by
hand.
5. Move the furnace gas valve manual control to the OFF
position.
6. Wait five minutes then smell for gas. Be sure to check near
the floor as some types of gas are heavier than air.
7. If you smell gas after five minutes, immediately follow the
instructions on page 4 of this manual. If you do not smell
gas after five minutes, move the furnace gas valve manual
control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the furnace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room temperature.
12. After the burners are lit, set the thermostat to desired
temperature.
F
S
URNACE
HUTDOWN
1. Set the thermostat to the lowest setting. The integrated control
will close the gas valve and extinguish flame. Following a 15
second delay, the induced draft blower will be de-energized.
After a 100 or 150 second delay period (field selectable), the
circulator blower will be de-energized.
2. Remove the burner compartment door and move the furnace
gas valve manual control to the OFF position.
3. Close the manual gas shutoff valve external to the furnace.
4. Replace the burner compartment door.
G
S
P
M
AS
UPPLY
RESSURE
T
O PREVENT UNRELIABLE OPERATION OR EQUIPMENT DAMAGE
I
NLET GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT
RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES
.
OPERATING
The line pressure supplied to the gas valve must be within the
range specified in the Inlet Gas Supply Pressure table. The supply
pressure can be measured at the gas valve inlet pressure tap or at
a hose fitting installed in the gas piping drip leg. The supply pres-
sure must be measured with the burners operating. To measure
the gas supply pressure, use the following procedure.
INLET
Gas Valve On/Off
Selector Switch
White-Rodgers Model 36G54 (Two-Stage)
EASUREMENT
CAUTION
OUTLET
Open to
Atmosphere
Inlet
Pressure
Tap
White-Rodgers Model 36G54 Connected to Manometer
Gas Valve On/Off
Selector Switch
,
THE
i
Outlet Pressure Tap
1/8 NPT
Honeywell Model VR9205 Connected to Manometer
1. Turn OFF gas to furnace at the manual gas shutoff valve
external to the furnace.
2. Connect a calibrated water manometer (or appropriate gas
pressure gauge) at either the gas valve inlet pressure tap
or the gas piping drip leg. See Honeywell VR9205 gas valve
figure or White-Rodgers 36G54 gas valve figure for location
of inlet pressure tap.
34
High Fire Regulator
Outlet
Adjust
Pressure Boss
Common
Terminal(C)
Regulator
Vent
Regulator
Vent
Low Fire
Regulator
Adjust
High Fire
Regulator
Adjust
Low Fire
Regulator
Adjust
Common
Terminal(C)
High Fire Coil
Terminal (HI)
Low Fire Coil
Terminal (LO)
Inlet Pressure Tap
1/8 NPT