4. REFRIGERANT FLOW DIAGRAM

4-1. Refrigerant Flow Diagram
Indoor Unit
SAP-K77RAX
SAP-K97RAX
SAP-K127RAX
n I
d
o
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation, both tubes must be well insulated with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
CAUTION
r o
u
n
t i
Wide tube
*1
Narrow tube
O.D.
6.35 mm
(1/4")
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Outdoor Unit SAP-C77RAX
O
u
d t
Wide tube
service
valve
Narrow
tube
service
valve
Capillary tube
*1 O.D. 9.52 mm (3/8") ... 77, 97 class
O.D. 12.7 mm (1/2") ... 127 class
Thickness:
Min. 8 mm
19
SAP-C97RAX
SAP-C127RAX
o
r o
u
n
t i
Compressor
Accumulator
Insulation
Wide tube
Cooling cycle
Thickness:
Min. 8 mm
Narrow tube