3-7. PROGRAMMING
(Continued)
Displayed Step
20
21
22
605
Blast chilling, low side air temperature limit, when using
the Frigiprobe, in step 12 of this section. Press
14 times and the low side air temperature, at which the com-
pressor cycles on and off, shows in the display. This tem-
perature is used in preventing the product from freezing, while in
the Chilling Mode, which is described in step 12.
The factory setting is -4ºF (-20ºC), but can be changed to a
maximum setting of 32ºF (0ºC), and a minimum setting of
-31ºF (-35ºC), by using
Blast chilling, high side air temperature limit, when using
the Frigiprobe, in step 12 of this section. Press
15 times and the high side air temperature, at which the com-
pressor cycles on and off, show in the display. This tempera-
ture is used in preventing the product from freezing, while in the
Chilling Mode, which is described in step 12.
The factory setting is 32ºF (0ºC), but can be changed to a
maximum setting of 50ºF (10ºC), and a minimum setting of
23ºF (-5ºC), by using
Frigiprobe, end of cycle temperature setting. Press
16 times, and the temperature at which ends the Probe Cycle
and starts the Hold Cycle, shows in the display.
The factory setting is 39ºF (4ºC) for blast chilling and
0ºF (-18ºC) for blast freezing. The blast chilling is factory set at
the maximum setting, but can be changed to a minimum setting
of 32ºF (0ºC), by using
The blast freezing temperature can be changed to a maximum
temperature of 32ºF (0ºC), and a minimum temperature
of -31ºF (-35ºC), by using
The maximum settings for U.S.A. is 39ºF (4ºC), and for
England is 37ºF (3ºC).
Model BCF-24/65/110, BCM-110
.
.
.
.