Operation Checklist; Refrigeration Capacities & Fan Speed - Henny Penny BCF-24 Operator's Manual

Blast chiller/freezer
Hide thumbs Also See for BCF-24:
Table of Contents

Advertisement

2-8. OPERATION CHECKLIST

2-9. REFRIGERATION
CAPACITIES &
FAN SPEED
1105
Using a container 4 inches (100 mm) deep, filled with hot water, insert
the Frigiprobe into the water and start the unit in the chilling mode.
Refer to the graph at left.
• The water temperature is probably below 145
1 won't be seen. The unit goes directly to phase 2.
• In phase 2, check that the compressor is regulating the air tempera-
ture limitation at around -4
read the air temperature, page 3-10.
• In phase 3, check that the compressor is regulating the air tempera-
ture limitation at around 32
read the air temperature, page 3-10.
• In phase 4, check that the compressor is regulating the air tempera-
ture limitation at around 37
directly from the display.
BCF-24
1000 W (3410 Btu/hr) at -4°F (-20°C) evaporation temperature
350 W (1190 Btu/hr ) at -40°F (-40°C) evaporation temperature
2950 RPM evaporator fan
BCF-65
1150 W (3930 Btu/hr) at -4°F (-20°C) evaporation temperature
400 W (1370 Btu/hr ) at -40°F (-40°C) evaporation temperature
2950 RPM evaporator fan
BCF/BCM-110
3500 W (11900 Btu/hr) at -4°F (-20°C) evaporation temperature
1000 W (3400 Btu/hr ) at -4°F (-40°C) evaporation temperature
2950 RPM evaporator fan
Model BCF-24/65/110, BCM-110
o
F (63
o
o
F (-20
C). Use P02 information to
o
o
F (0
C). Use P02 information to
o
o
F (3
C). Read the air temperature
o
C), so phase
2-7