Harman PB 105 Installation & Operating Manual
Harman PB 105 Installation & Operating Manual

Harman PB 105 Installation & Operating Manual

Pellet boiler

Advertisement

Quick Links

The harman pb 105 pellet boiler
WArNINg! rISk OF FIrE Or ExplOISION!
ImprOpEr INSTAllATION, OpErATION Or mAINTENANCE OF ThIS bOIlEr CAN CAuSE INjurY Or
dEATh.
FOllOW All INSTruCTIONS CONTAINEd IN ThIS mANuAl
bEFOrE INSTAllATION ANd uSE OF ThIS bOIlEr:
plEASE rEAd ANd uNdErSTANd ThIS ENTIrE mANuAl.
CONSulT YOur lOCAl AuThOrITIES hAvINg jurISdICTION.
CONTACT YOur muNICIpAl buIldINg dEpArTmENT, FIrE dEpArTmENT, Or OThEr lOCAl
AuThOrITIES bEFOrE INSTAllINg ThIS bOIlEr.
lOCAl buIldINg rEgulATIONS mAY rEquIrE SpECIAl pErmITS, rESTrICTIONS ANd INSpECTION
rEquIrEmENTS.
Installation & Operating manual
"Ce manuel est disponible en Français sur demande"
SAFETY NOTICE
SAvE ThESE INSTruCTIONS
r11
manual #3-90-07205

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PB 105 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Harman PB 105

  • Page 1 Installation & Operating manual The harman pb 105 pellet boiler “Ce manuel est disponible en Français sur demande” SAFETY NOTICE WArNINg! rISk OF FIrE Or ExplOISION! • ImprOpEr INSTAllATION, OpErATION Or mAINTENANCE OF ThIS bOIlEr CAN CAuSE INjurY Or dEATh.
  • Page 3 parts locations...
  • Page 4: Table Of Contents

    Introduction Table Of Contents Warranty Appliance Certification. Assembly model: Pellet Burning Boiler - PB105 Test lab: Omni-Test Laboratories, Inc. venting report #: 135-S-16-6 Type: Pellet Fueled Central/Supplementary For Installation Residential Use Standard(s): CAN/CSA B366.1-M91, and Fuel Specifications UL 391 Operation maintenance Note: This appliance is also approved for Troubleshooting...
  • Page 5: Warranty

    Warranty HARMAN™ CENTRAL HEATING PRODUCTS LIMITED WARRANTY Hearth & Home Technologies Inc., on behalf of its Harman™ brand (”HHT”), extends the following warranty for all Harman™ furnace and boiler products (“Products”) that are purchased from an HHT authorized dealer. Warranty Coverage: Subject to the conditions, exclusions and limitations set forth below, HHT warrants to the origi- nal owner of the Products, and to any transferee taking ownership of the Products at the site of original installation within two years following the date of original purchase, that the Products will operate free from defects in material and workmanship under normal conditions and use, as described in the operating instructions furnished with the Prod-...
  • Page 6: Assembly

    Assembly Installation of the Flue Tunnel Weldment, Boiler Kit Materials: (Refer to page 3) Combustion Blower and Wiring, ESP and Heat List of items contained within the boiler kit shipped with Shield: the unit. Step 1: First install the flue tunnel weldment by 1 - Control board cover aligning the (4) studs with the (4) holes in the ash 1 - Access cover (Hopper Swing Plate Knob)
  • Page 7 Assembly Refer to the illustration on page 3 to identify the compo- MINIMUM NON-COMBUSTIBLE FLOOR PROTECTION AREA nents listed below: 1. Install the control board cover as well as the access cover located on the feeder cover. 2. Install the spring handles provided with the unit on the NON-COMBUSTIBLE ash door, firebox door and the heat exchanger cleanout rod FLOOR PROTECTOR...
  • Page 8 Assembly INSTALLATION IS TO BE PERFORMED BY A QUALIFIED INSTALLER. NOTE: All installation clearances and restrictions must be adhered to. NOTE:Use only 4” diameter type “L” or “PL” venting system. Be sure to inspect and clean exhaust venting system frequently.
  • Page 9: Venting

    venting Requirements for Terminating the Venting above a gas meter/regulator assembly when measured from the horizontal center-line of the regulator. WARNING: Venting terminals must not be recessed into I. The clearance to service regulator vent outlet must be a wall or siding. a minimum of 6 feet.
  • Page 10 venting Fig. 3 Avoiding Smoke and Odors - Negative Pressure, To reduce the probability of reverse drafting dur- Shut-down and Electrical Power Failure. ing shut-down conditions, Hearth & Home Tech- To reduce the probability of back-drafting or burn nologies strongly recommends: back in the pellet boiler during a power failure, •...
  • Page 11 Venting venting Venting Use 4” pellet vent pipe only. A combustion blower is used to extract the combustion gases from the firebox. This creates a negative pressure in the firebox and a positive pressure in the venting system as shown in Fig. 4. The longer the vent pipe and more elbows used in the system, the greater the flow resistance.
  • Page 12: Installation

    venting Installation NOTE: Use only 4” diameter approved pellet venting system. Be sure to inspect and clean exhaust venting system frequently. INSTALLATION IS TO BE PERFORMED BY A QUALIFIED INSTALLER. DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
  • Page 13 Installation Outside Air To install outside air, use 2 3/4” I.D.galvanized steel flex pipe, part # 2-00-08544 ( 12’ 6” length) or part # 2-00-08545 ( 25’ length) See Fig. 6. There is a break- away hole on the rear panel which must be removed before connecting the flex pipe.
  • Page 14 main Wiring Installation...
  • Page 15 Installing Duct Installation NOTE: Cold return water temperature (Sustained temperatures below 140 degrees Fahrenheit) will lead to condensation in the firebox. This moisture can lead to creosote formation. To help minimize moisture and creosote, it is strongly recommended that some form of temperature balance is incorporated into the return water system. NOTICE: When installing with the atmospheric conversion: All of the pressurized system components shown are not nec- essary.
  • Page 16 Installing Duct/Air Conditioning Installation Boilers intended to be connected to an existing boiler or boiler system shall: 1. Be capable of being installed without interfering with the normal delivery of heated water from the original boiler to the radiation system. 2.
  • Page 17 Installation EXAMPLE OF TYPICAL TANKLESS DOMESTIC HOT WATER PIPING HIGH TEMPERATURE TEMPERED HOT WATER TO WATER (IF NEEDED) SHOWERS AND FAUCETS NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS OPTIONAL DOMESTIC RECOMMENDED INSTALLATION INSTRUCTIONS FOR THE PROPER HOT WATER COIL MOUNTING POSITION AND LOCATION WITHIN THE PIPING SYSTEM. INLET MIXING VALVE OUTLET...
  • Page 18 Installation NOTE: ALWAYS REFER TO THE INDIVIDUAL COMPONENTS RECOMMENDED TYPICAL BOILER HOT WATER PIPING SHOWING AIR REMOVAL SYSTEM, PROVISIONS FOR THE EXPANSION OF INSTALLATION INSTRUCTIONS FOR THE PROPER MOUNTING POSITION AND WATER AND THE AUTOMATIC COLD WATER SUPPLY. ALSO SHOWN IS THE AUTOMATIC MIXING VALVE. THIS LOCATION WITHIN THE PIPING SYSTEM.
  • Page 19 Installation NOTE: Cold return water temperature (Sustained temperatures below 140 degrees Fahrenheit) will lead to condensation in the firebox. This moisture can lead to creosote formation. To help minimize moisture and creosote, it is strongly recommended that some form of temperature balance is incorporated into the return water system. NOTICE: When installing with the atmospheric conversion: All of the pressurized system components shown are not nec- essary.
  • Page 20 Over heat Safety Zone OverHeat Safety Zone (Dump Zone): STRONGLY RECOMMENDED in all installations. When the pellet boiler is operating at High burn, and all demand from the heating system stops, the control will reduce the feed rate and shut down completely as necessary. This may take several minutes, and the remain- ing heat may cause the water temperature to continue to rise.
  • Page 21 Installation Draft Test Procedure After the venting is completed, the firebox low draft will need to be checked and possibly adjusted. After Firebox Door removing the 3/8” bolt from the draft hole shown in Fig. 9, insert the draft meter tube. The appliance doors and Draft Bolt Location hopper lid must be latched during this test.
  • Page 22: Fuel Specifications

    Fuel Specifications Fuel and Fuel Storage Performance Pellet fuel quality can fluctuate from manufacturer to • Higher ash content requires more frequent mainte- manufacturer, and even from bag to bag. nance. Hearth & Home Technologies recommends using only • “Premium” grade pellets will produce the highest fuel that is certified by the Pellet Fuels Institute (PFI).
  • Page 23: Operation

    Operation Power Light Feed adjuster Indicates power to the Sets the maximum feed rate control board. Test Combustion blower, feed motor Status Light and safety dump zone are fully Will be lit anytime there is a energized for the first minute. Afterward, combustion blower call for heat.
  • Page 24: Water Temperature

    Operation Setting The Boiler Temperature Without the Outdoor Air Temperature Sensor Installed To set the maximum boiler water temperature, sim- ply turn the Max. Temp. water temperature dial to the desired setting. The control and the boiler will then perform to achieve and maintain the set temperature. The Min.
  • Page 25 Operation...
  • Page 26 Operation Starting A Fire Automatically 1. Turn Mode Selector to “OFF”. This resets the control in addition to turning it off. 2. Clean Burnpot with scraper, if necessary. This is usually a weekly maintenance proce- dure. Cleaning the burn pot with the scraper with a small amount of new fuel in the bottom is not a problem.
  • Page 27 Operation 4. If Starting After an Empty Hopper, Turn Feed Adjuster to “TEST” (for one 60 second cycle). This will feed pellets into the auger tube and also allow you to check the motors for operation. NOTE: The auger motor will not operate with any of the doors open.
  • Page 28 Operation 7. Open hopper swing plate as shown in Fig. 13 (See “NOTE” on page 26.) 8. Turn the MIN. TEMP. Dial on the control board to the desired Minimum temperature. This will start the lighting process if the temperature at the aquastat sensor is approximately 5°...
  • Page 29: Plumbing System

    Operation 11. Apply starting gel as shown in Fig.15 12. Light The Starting Gel With A Match. Fig. 15 NOTE: Stirring the starting gel into the pellets usually 13. Close The Doors allows the fire to become established quicker. The fire will light and the control will adjust the fire to the proper level according to the MAX TEMP dial CAUTION: A vapor flash could occur if too much setting.
  • Page 30: Maintenance

    maintenance Burnpot Cleaning: The burnpot should be cleaned no less than once a week. For best operation the burnpot should be cleaned every time the hopper is filled with pellets. The fire does not have to be out to scrape the burnpot although it is recommended the boiler be on minimum burn at the time of cleaning.
  • Page 31 maintenance Ash Pan Handle Ash Door Ash Pan Ash Door Handle Fig. 21 Disposal of Ashes WARNING! RISK OF FIRE! Ashes should be placed in a steel container with a tight • Ash, soot or creosote build-up may cause fitting lid. The closed container of ashes should be moved overheating or fire.
  • Page 32 maintenance Heat Exchanger Cleanout Rod Handles Firebox Door Heat Exchanger Tube Secondary Ash Chamber Access Plate Fines Cleanout Cover Firebox Wall Ash Door Cleaning -Open the ash door and remove the ash pan. Dispose This cleaning should be done after each ton of pellets of any ash that has accumulated in the ash pan as well used.
  • Page 33 maintenance The boiler MUST be OFF and COOL before you should attempt to clean the combustion blower. The wire to the combustion blower doesn’t need to be disconnected during the cleaning process. Loosen the three (3) thumb screws about 4 turns each. See Fig.
  • Page 34: Troubleshooting

    Troubleshooting FEEdEr dOES NOT FEEd SmOkE IS vISIblE COmINg OuT OF vENT 1. No pellets in hopper. 1. Air-fuel ratio is too rich. 2. Firebox draft may be too low for low draft pres- A. Feed rate too high. sure switch in feeder circuit to operate. Check B.
  • Page 35: Atmospheric Conversion

    Atmospheric Conversion Atmospheric Conversion: Item # 1-00-232200, provides automatic fill, and converts the heating system plumbing from pressurized to a zero pressure system. Allows for installation into more places where codes and standards restrict pressurized systems. Note that when using the atmo- spheric conversion, air bleeders and check valves may actually allow air into the lines.
  • Page 36: Service Parts

    pb105 Service parts beginning manufacturing date: N/A Central heat Ending manufacturing date: Active 1-90-07205 IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement Stocked parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer. at depot ITEm dESCrIpTION...
  • Page 37 pb105 Service parts beginning manufacturing date: N/A Ending manufacturing date: Active #8 Ash base Assembly 8.20 8.19 8.18 8.17 8.16 8.10 8.11 8.12 8.13 8.14 8.15 IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement parts for Stocked your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer.
  • Page 38 pb105 Service parts beginning manufacturing date: N/A Ending manufacturing date: Active IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement Stocked parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer. at depot ITEm dESCrIpTION...
  • Page 39 pb105 Service parts beginning manufacturing date: N/A Ending manufacturing date: Active #28 Feeder Assembly 28.1 28.15 28.12 28.16 28.14 28.2 28.13 28.11 28.3 28.10 28.9 28.4 28.5 28.8 28.7 28.6 IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement Stocked parts for your appliance please provide model number and serial number.
  • Page 40 pb105 Service parts beginning manufacturing date: N/A Ending manufacturing date: Active IMPORTANT: THIS IS DATED INFORMATION. When requesting service or replacement Stocked parts for your appliance please provide model number and serial number. All parts listed in this manual may be ordered from an authorized dealer. at depot ITEm dESCrIpTION...
  • Page 41: Specifications

    Specifications...
  • Page 42: Wiring Diagram

    Wiring diagram...
  • Page 43 power Failure backup Supply...
  • Page 44: Testing Label

    Testing label Wood WARNING: Risk of fire - ATTENTION: Risque de feu - Do not operate with the flue draft Ne fonctionnez pas avec l'ébauche exceeding -.9 in Water Column / -224Pa. deconduite de cheminée excédant -.9 " colonne de l'eau / -224Pa. Hearth &...
  • Page 45 Service record / Notes...
  • Page 46 Service record / Notes...
  • Page 47 Proudly Printed On 100% Recycled Paper...