Installation Of Indoor, Outdoor Unit - LG LB-F3660HL Manual

Ceiling duct type air conditioner
Table of Contents

Advertisement

Installation of Indoor, Outdoor Unit

1. Selection of the best location
1) Indoor unit
Select location
Install the air conditioner in the location that satis-
fies the following conditions.
• The place shall easily bear a load exceeding four
times the indoor unit's weight.
• The place shall be able to inspect the unit as the
figure.
• The place where the unit shall be leveled.
• The place shall allow easy water drainage.(Suit-
able dimension "H" is necessary to get a slope to
drain as figure.)
• The place shall easily connect with the outdoor
unit.
• The place where the unit is not affected by an
electrical noise.
• The place where air circulation in the room will be
good .
• There should not be any heat source or steam
near the unit.
2) Outdoor unit
• If an awning is built over the unit to prevent
direct sunlight or rain exposure, be careful that
heat radiation from the condenser is not restrict-
ed.
• There should not be any animals or plants which
could be affected by hot air discharged.
• Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
Top view
(unit: mm)
600
Front view
More than
30cm
F e
n c
o b
e o
s t a
r
c l e
s
- 14 -
Inspection hole
(600X600)
Control box
600
Front
H
More than
30cm
More than
70cm
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lb-f3660cl

Table of Contents