4. Heating Mode Operation (Except Cooling Model)
The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.
Intake Air temp.
Setting temp.+3°C
(Compressor OFF)
Setting temp.
(Compressor ON)
INDOOR FAN
COMPRESSOR
A point; While the indoor Heat-Exchanger temperature is higher than 40°C fan operates at low speed, when
it becomes lower than 40˚C fan stops.
B point; When the indoor Heat-Exchanger temperature is higher than 42°C, fan operates at seleted fan
speed, when it becomes lower than 39°C, the fan operates at low speed.
5. Hot-Start Control
The indoor fan stops until the evaporator piping temperature will be reached to 31°C.
The operation diagram is as following.
Copyright ©2008 LG Electronics. Inc. All right reserved.
Only for training and service purposes
minimum 3min
minimum
1min
10sec.
Selecting
Hot Start
Low
Fan Speed
ON
PIPING
TEMPERATURE
31°C
28°C
INDOOR FAN
COMPRESSOR
: Selected Fan
A
B
Low
OFF
Low
OFF
1min
ON
: Low Fan
: Fan Stop
- 12 -
minimum
10sec.
Selecting fan
Low
speed
ON
OFF
LGE Internal Use Only
A
OFF