2. Guideline for each installation process
2.3.1 Drain pipe slope and support
• Slope gradient for drain should be 1/50~1/100 and PVC pipes should be used.
• Support hanger should be at 1(3.28)~1.5(4.92) (m(ft)) interval to prevent from loosing and dropping.
• Drain pipe insulation
: The inside temperature of drain pipe is about 10℃(50℉). When high temperature and humidity air touches the sur-
face of pipe, dew condensation occurs. To prevent that, drain pipe keeps warm using insulation with polyethylene
10mm(0.39inch) thickness.
Indoor unit
Or
Outdoor unit
1. Application
Refrigerant pipe length contracts and expands on heating and cooling repeatedly. So supporting work is needed not to
hinder each copper pipe connection part.
2. Supporting distance for common drain pipe
[Table]The interval of the supporting hanger for drainage pipe
Pipe diameter
Ø20(25/32)~40(1-9/16)
[mm(inch)]
Max. interval[m(ft)]
3. Anchor bolt supporting work
Anchor bolt supporting work should be used for supporting a heavy indoor unit to ceiling.
Clamp hanger supporting work is for hanging refrigerant pipe, drain pipe and cables.
It can prevent vibrating noise from passing through pipe.
We recommend set anchor bolt for supporting indoor unit and strong anchor bolt for supporting pipes and cables
Below 1.0(3.28)
Gradient of at least 1 / 50 ~ 1 / 100
Ø40(1-9/16)~50(1-31/32)
Below 1.2(3.94)
Ø65(2-9/16)~125(4-15/16)
Below 1.5(4.92)
Heat pump 60Hz/R410A