Electric Characteristics - LG ATNH24GPLE2 User Manual

Single zone heat pump 60hz/r410a 6csl0-01b (replaces 6csl0-01a)
Hide thumbs Also See for ATNH24GPLE2:
Table of Contents

Advertisement

SINGLE ZONE
1. DC Inverter SINGLE ZONE

1.10 Electric characteristics

Unit
Model
AUUW24GD2 [LUU247HV]
AUUW42GD2 [LUU427HV]
Notes :
1. Voltage range
Voltage supplied to the unit terminals should be within the
minimum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOP
MCA = (1.25 x Load1) + Load2 + Load3
MOP = (2.25 x Load1) + Load2 + Load3
- Load1 : Rated running current of largest motor
(compressor or other motor)
- Load2 : sum of current for all other motors
- Load3 : any other load rated 1.0A or more
4. Select wire spec. based on the MCA
5. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
6. MSC & RLA are measured as the compressor only test
condition.
7. OFM is measured as the outdoor unit test condition
Phase
Hz
Voltage
MCA
18.1
Min.:187,
1
60
Max.:253
24.1
Power
Compressor
RLA
MOP
MSC
Cooling Heating
31.6
-
10.0
41.6
-
15.5
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Heat pump 60Hz/R410A
OFM
kW
FLA
13.5
0.124
0.6
17.5
0.124 x 2 0.6 x 2
_ 13