Fig. 9. Inserting wires in terminal block.
IMPORTANT
Use 18-gauge thermostat wire.
Table 2. Terminal Designation Descriptions.
THM5421C1008
Terminal
Designations
1
Terminal 1—data to/from thermostat
2
Terminal 2—power from thermostat (24Vac)
3
Terminal 3—common from thermostat
(24Vac)
C
24 Vac Transformer Common
R
24 Vac Transformer
RC
24 Vac Cooling Transformer
RH
24 Vac Heating Transformer
HUM1/HUM2
Humidification Connection (normally open)
DHM1/DHM2
Dehumidification Connection (normally
open or closed based on installer setup)
VNT1/VNT2
Ventilation connection (normally open)
W1/O/B
Stage 1 Heating Relay (Conventional)
Change-over Relay (Heat Pump)
W2/AUX
Stage 2 Heating Relay (Conventional)
Auxiliary Heat (fossil fuel or electric) (Heat
Pump)
W3/AUX2
Stage 3 Heating Relay (Conventional)
Auxiliary Heat (fossil fuel or electric) (Heat
Pump)
Y
Stage 1 Compressor Relay
Y2
Stage 2 Compressor Relay
G
Fan Relay
L
Heat Pump Equipment Monitor
OUT1/OUT2
Outdoor Temperature Sensor
IN1/IN2
Remote Indoor Temperature Sensor
DATS1/DATS2
Discharge Air Temperature Sensor
68-0287—04
M23541
Function
6
NOTES:
1.
When used in a single-transformer system, leave
the metal jumper wires in place between R and Rc,
and Rc and Rh. If used on a two-transformer sys-
tem, remove metal jumper wire between Rc and Rh.
2.
If thermostat is configured for a heat pump system
in the Installer Setup, configure changeover valve
for cool (O-factory setting) or heat (B).
For wiring to a W8835 Zone panel please refer to the product
data sheet included with the panel.
1
1
1
2
2
3
3
C
R
RC
RH
FACTORY INSTALLED
JUMPER BETWEEN R,
RC AND RH
1
WIRE TO TERMINALS ON THERMOSTAT.
Fig. 10. Typical hookup of conventional single-stage heat
and cool system with single transformer
(1H/1C conventional).
1
1
2
3
OIL PRIMARY/
FACTORY INSTALLED JUMPER BETWEEN R,
AQUASTAT
AND RC (REMOVE FACTORY INSTALLED
JUMPER BETWEEN RC AND RH
1
WIRE TO TERMINALS ON THERMOSTAT.
Fig. 11. Typical hookup of conventional single-stage heat
and cool system with oil primary (1H/1C conventional).
COMMUNICATION LED
COMMUNICATION
CONV. HP
TERMINALS
W1
O/B
W2
AUX
24 VAC
W3
AUX2
Y
Y
Y2
Y2
G
G
COMMUNICATION LED
1
COMMUNICATION
CONV. HP
2
TERMINALS
W1
O/B
3
W2
AUX
C
24 VAC
W3
AUX2
R
Y
Y
RC
Y2
Y2
RH
G
G
M23485
M23486