Honeywell SERIES 2000 T7300D User Manual page 4

Series 2000 commercial microelectronic thermostat
Table of Contents

Advertisement

T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Installer Setup
Number
(Press
Unoccupied
Temp key
to change)
Select
9
Cooling cycle
rate
10
11
System setting
12
adjustment
(models with
System key)
Degree tempera-
14
ture display
Clock format
16
Intelligent Fan™
17
operation
Auxiliary Contact
18
Operation
Extended fan
19
operation in
heating
Fan key
21
adjustment
(models with Fan
key only)
Remote sensing 22
Keypad lockout
25
level (keypad
lockout is
enabled and
disabled by DIP
switch 1 on back
of thermostat)
Duration of
26
temporary
override
Minimum off time
33
for the
compressor
62-0123—3
Table 2. Thermostat Installer Setup Options (Continued).
Factory-Setting
Display
Description
4
Stage 1—4 cph
4
Stage 2—4 cph
4
Stage 3—4 cph
Depends
System selection
on model
0
Temperature is
displayed in F
0
12-hour clock format
2
Fan operates
continuously in
Occupied and
Recovery mode. Fan
operates with call for
heating or cooling in
Unoccupied mode.
0
0—Time of day
contacts
0
No extended fan
operation after the call
for heat ends
0
Fan setting key is
operational
0
Remote sensing not
activated
0
No lockout
3
3—Three hour
override
4
4 minute minimum off
time for the
compressor
Other Choices
(Press
Display
3
3—3 cph
0, 1 or 2 0—System setting key is
operational
1—Auto setting is disabled
2—Auto only setting
1
Temperature is displayed in
C
1
24-hour clock format
0 or 1
0—Fan only operates with
calls for heating or cooling
in Occupied and
Unoccupied modes.
1—Fan operates
continuously in Occupied
mode. Fan operates with
calls for heating or cooling
in Unoccupied mode.
1
1—Economizer contacts
1
Fan operation is extended
90 seconds after the call for
heat ends.
1
Fan setting key is Auto only
1
Remote sensing activated
1 or 2, 3 1—Lockout all keys on
thermostat except system
and fan settings, temporary
setpoint, clock and day
adjustments
2—Lockout all keys except
Set Current Day/Time,
increase
3—Lockout all keys except
Temporary Occupied, Set
Day and Clock keys
1, 8 or 12 1—One hour override
8—Eight hour override
12—Twelve hour override
0, 1, 2, 3
Minimum number of minutes
or 5
(0 thru 5) the compressor will
be off between calls for the
compressor
4
or
key to change)
Description
and decrease
keys.
(continued)
Actual
Setting

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

T7300d

Table of Contents