INSTALLER SYSTEM TEST

Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.
Table 3. Tests Available in Installer System Test.
Test
Number
System Test Description
10 to 19
Heating equipment can be turned on and off
30 to 39
Cooling equipment can be turned on and off
40 to 49
Fan equipment can be turned on and off
60 0 to
Keyboard keys test
60 19
70 to 79
Thermostat information including date code,
software versions and subbase identification
are displayed
To start the system test:
CAUTION
The minimum off time for compressors is bypassed
during the Installer System Test. Equipment
damage can occur if the compressor is cycled too
quickly.
Key to
Press
Heating Equipment System Test
Heat/Cool Settings
62-0123—3
AM
Set Temperature
Change
Time/Temp
Occupied
Unoccupied
Day
Temp
Temp
Mon
Occupied 1
Heat/Cool
Copy
Settings
System
System
Fan
Heat
Table 4. Installer System Test Options.
Test
Number
10
Enter heating equipment system test.
11
Stage-one heat comes on. When Installer Setup number 02 is 01, the system fan
is also energized.
12
Stage-two heat comes on. Stage-one heat and system fan remain on.
13
Stage-three heat comes on. Stage-one and stage-two heat with the system fan
are on.
12
Stage-three heat turns off.
11
Stage-two heat turns off.
10
Stage-one heat and system fan turn off.
Press and hold the increase
the same time, until 10 appears. All segments of the LCD
are displayed for three seconds before 10 appears. See
Room
Fig. 5 and 6.
Fan
Auto
M4954A
Set Program
Set Program
Em Ht
Em Ht
Aux Ht
Aux Ht
Comm
Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System
Em Heat
Off
Fig. 5. Display of all the segments of the LCD.
Refer to Table 4 and Thermostat Information section for
directions and results of the specific system tests.
NOTE: Press Run Program to exit the system test. The
system test times out after four minutes without
any key presses.
Description
6
and
Temporary Setting Enrg
Start Time
Set Day/Time
Set Day/Time
AM
PM
Heat
In
Recovery
Lo
Med
Hi
Cool
Auto
Wait
TEST NUMBER
Fig. 6. Display of test number.
decrease keys, at
Sav
Room
%Humid
Cool
Remote
Auto
Only
Duct
Fan
On
Auto
M4916
M10257A
(continued)