Honeywell SERIES 2000 T7300D User Manual page 3

Series 2000 commercial microelectronic thermostat
Table of Contents

Advertisement

Set Program
Set Program
Start Time
Set Day/Time
Set Day/Time
Em Ht
Em Ht
Aux Ht
Aux Ht
Comm
Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System
Off
Cool
Auto
Em Heat
Fig. 3. Display of all the segments of the LCD.
INSTALLER SETUP
NUMBER DISPLAY
(COLUMN 2
OF TABLE 2)
Fig. 4. Display of Installer Setup number and setting.
Installer Setup
Number
(Press
Unoccupied
Temp key
to change)
Select
Not used
1
Fan operation
2
Output stages of
3
heating
4
Heating cycle
rate
5
6
Not used
7
Output stages
8
of cooling
T7300D SERIES 2000 COMMERCIAL MICROELECTRONIC THERMOSTAT
Temporary Setting Enrg
AM
Room
PM
%Humid
Heat
Cool
Remote
Recovery
Only
In
Auto
Lo
Med
Hi
Fan
Wait
On
FACTORY SETTING
OR OTHER CHOICE
DISPLAY (COLUMN 3
OR 5 OF TABLE 2)
Table 2. Thermostat Installer Setup Options.
Factory-Setting
Display
0
Conventional applica-
tions where equipment
controls fan operation
in heat mode
Depends
Stages of heat
on
subbase
6
Stage 1—4 cph
6
Stage 2—4 cph
6
Stage 3—4 cph
Depends
Three stages of cool
on
subbase
— To advance to the next Installer Setup number, press
the Unoccupied Temp key.
Sav
— To return to a previous Installer Setup number, press
the Heat/Cool Settings key.
— To change a setting, use the increase
Duct
decrease key.
— To exit the Installer Setup, press the Run Program
Auto
key. The Installer Setup is automatically exited if no
key presses are made for four minutes.
M4916
Installer Setup numbers are listed in Table 2.
CAUTION
Electric heat systems must be configured correct-
ing in Installer Setup 2 to prevent equipment
damage caused by the system running without
the fan.
IMPORTANT
Only configurable numbers are shown on the
device. Example: If thermostat does not have a
M10238B
system key, Installer Setup Number 12 will not be
displayed. Review Table 2 factory-settings and
mark any desired changes in the Actual Setting
column. When Installer Setup is complete,
review the settings to confirm that they match
the system.
Description
Display
1
0, 1, 2,
or 3
8
0, 1, 2
or 3
3
Other Choices
(Press
or
key to change)
Description
Electric heat applications
where thermostat controls
fan operation in heat mode
0—No heating
1—One stage of heat
2—Two stages of heat
3—Three stages of heat
3, 4, 8, 9 cph
0—No cooling
1—One stage of cool
2—Two stages of cool
3—Three stages of cool
or
Actual
Setting
(continued)
62-0123—3