Twj/Twe Heating - Trane TWE030CA Product Data

Heat pump split system air conditioning 30 to 50 mbh - 50 hz air handler models,condensing models
Table of Contents

Advertisement

O.D.
HEATING CAPACITY (BTUH/1000) AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
F.
60
70
75
-18
0.00
0.00
0.00
-13
0.00
0.00
0.00
-8
0.00
0.00
0.00
-3
0.00
0.00
0.00
2
6.79
6.60
6.50
7
8.13
7.90
7.78
12
9.48
9.20
9.06
17
10.8
10.5
10.3
22
11.2
10.9
10.7
27
11.6
11.2
11.0
32
11.9
11.6
11.4
37
12.3
11.9
11.8
42
12.7
12.3
12.1
47
18.9
18.3
18.0
52
20.2
19.6
19.3
57
21.6
20.9
20.6
62
22.9
22.2
21.8
67
24.3
23.5
23.1
72
25.6
24.8
24.4
O.D.
HEATING CAPACITY (BTUH/1000) AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
F.
60
70
75
-18
0.00
0.00
0.00
-13
0.00
0.00
0.00
-8
0.00
0.00
0.00
-3
8.10
7.93
7.85
2
9.91
9.70
9.60
7
11.7
11.5
11.3
12
13.5
13.2
13.1
17
15.3
15.0
14.8
22
16.2
15.9
15.7
27
17.1
16.7
16.5
32
18.0
17.6
17.4
37
18.9
18.4
18.2
42
19.8
19.3
19.1
47
26.2
25.6
25.3
52
28.0
27.4
27.0
57
29.8
29.1
28.8
62
31.6
30.9
30.5
67
33.5
32.7
32.3
72
35.3
34.4
34.0
O.D.
HEATING CAPACITY (BTUH/1000) AT
TEMP.
INDICATED INDOOR DRY BULB TEMP.
F.
60
70
75
-18
0.00
0.00
0.00
-13
0.00
0.00
0.00
-8
0.00
0.00
0.00
-3
9.79
9.60
9.51
2
11.8
11.6
11.5
7
13.9
13.6
13.5
12
15.9
15.6
15.4
17
18.0
17.6
17.4
22
18.9
18.5
18.3
27
19.9
19.5
19.3
32
20.9
20.4
20.2
37
21.8
21.4
21.2
42
22.8
22.3
22.1
47
30.2
29.6
29.3
52
32.3
31.6
31.3
57
34.3
33.6
33.2
62
36.4
35.6
35.2
67
38.4
37.6
37.2
72
40.5
39.6
39.2
Performance
Data Heating
TWJ020CA WITH TWE030CA4 AT 700 CFM
TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
80
60
70
75
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
6.41
1.47
1.54
1.58
7.67
1.50
1.57
1.61
8.92
1.52
1.60
1.63
10.2
1.55
1.63
1.66
10.5
1.56
1.64
1.68
10.9
1.57
1.65
1.69
11.2
1.58
1.66
1.70
11.6
1.60
1.68
1.71
11.9
1.61
1.69
1.73
17.7
1.71
1.79
1.84
19.0
1.73
1.82
1.87
20.2
1.76
1.85
1.90
21.5
1.79
1.88
1.92
22.7
1.81
1.91
1.95
24.0
1.84
1.93
1.98
TWJ024CA WITH TWE030CA4 AT 900 CFM
TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
80
60
70
75
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
7.77
1.86
1.94
1.98
9.49
1.92
2.01
2.06
11.2
1.99
2.08
2.13
12.9
2.06
2.15
2.20
14.7
2.12
2.22
2.27
15.5
2.18
2.28
2.33
16.3
2.23
2.34
2.39
17.2
2.29
2.40
2.45
18.0
2.34
2.45
2.51
18.9
2.39
2.51
2.57
25.0
2.52
2.65
2.71
26.7
2.59
2.72
2.78
28.4
2.66
2.79
2.86
30.2
2.72
2.86
2.93
31.9
2.79
2.93
3.00
33.6
2.86
3.00
3.07
TWJ030CA WITH TWE030CA4 AT 1000 CFM
TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
80
60
70
75
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
9.41
2.27
2.38
2.44
11.4
2.36
2.47
2.53
13.3
2.44
2.56
2.62
15.3
2.53
2.65
2.72
17.2
2.61
2.74
2.81
18.2
2.69
2.83
2.89
19.1
2.77
2.91
2.98
20.0
2.85
2.99
3.06
20.9
2.92
3.07
3.15
21.8
3.00
3.16
3.23
29.0
3.12
3.28
3.37
30.9
3.21
3.37
3.46
32.9
3.29
3.46
3.55
34.8
3.38
3.55
3.64
36.8
3.46
3.64
3.74
38.7
3.55
3.73
3.83
16
English Units
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 700 CFM TIMES CORR. FACTOR
80
= VALUE AT NEW AIRFLOW)
0.00
AIRFLOW
0.00
HEATING CAP.
0.00
COMPR. KW
0.00
VALUES AT ARI RATING CONDITIONS OF:
1.61
70&47/43 (HIGH TEMP. POINT)
1.64
70&17/15 (LOW TEMP. POINT)
1.67
AIRFLOW = 700 CFM
1.70
HEATING CAP. (HIGH TEMP.) = 18300 BTUH
1.71
HEATING CAP. (LOW TEMP.) = 10500 BTUH
1.73
COMPR. POWER (HIGH TEMP.) = 1354 WATTS
1.74
COMPR. POWER (LOW TEMP.) = 1185 WATTS
1.75
COEFF. OF PERF. (HIGH TEMP.) = 3.00
1.77
COEFF. OF PERF. (LOW TEMP.) = 1.88
1.88
OUTDOOR FAN POWER = 130 WATTS
1.91
INDOOR FAN POWER = 310 WATTS
1.94
NOTE: RATED WITH 25 FEET OF 3/4
1.97
SUCTION AND 5/16 LIQUID LINE
2.00
2.03
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 900 CFM TIMES CORR. FACTOR
80
= VALUE AT NEW AIRFLOW)
0.00
AIRFLOW
0.00
HEATING CAP.
0.00
COMPR. KW
2.03
VALUES AT ARI RATING CONDITIONS OF:
2.10
70&47/43 (HIGH TEMP. POINT)
2.17
70&17/15 (LOW TEMP. POINT)
2.25
AIRFLOW = 900 CFM
2.32
HEATING CAP. (HIGH TEMP.) = 25600 BTUH
2.38
HEATING CAP. (LOW TEMP.) = 15000 BTUH
2.44
COMPR. POWER (HIGH TEMP.) = 2038 WATTS
2.51
COMPR. POWER (LOW TEMP.) = 1614 WATTS
2.57
COEFF. OF PERF. (HIGH TEMP.) = 2.84
2.63
COEFF. OF PERF. (LOW TEMP.) = 1.96
2.77
OUTDOOR FAN POWER = 180 WATTS
2.85
INDOOR FAN POWER = 430 WATTS
2.92
NOTE: RATED WITH 25 FEET OF 3/4
3.00
SUCTION AND 5/16 LIQUID LINE
3.07
3.14
CORRECTION FACTORS - OTHER AIRFLOWS
(VALUE AT 1000 CFM TIMES CORR. FACTOR
80
= VALUE AT NEW AIRFLOW)
0.00
AIRFLOW
0.00
HEATING CAP.
0.00
COMPR. KW
2.49
VALUES AT ARI RATING CONDITIONS OF:
2.59
70&47/43 (HIGH TEMP. POINT)
2.69
70&17/15 (LOW TEMP. POINT)
2.78
AIRFLOW = 1000 CFM
2.88
HEATING CAP. (HIGH TEMP.) = 29600 BTUH
2.96
HEATING CAP. (LOW TEMP.) = 17600 BTUH
3.05
COMPR. POWER (HIGH TEMP.) = 2649 WATTS
3.14
COMPR. POWER (LOW TEMP.) = 2109 WATTS
3.22
COEFF. OF PERF. (HIGH TEMP.) = 2.64
3.31
COEFF. OF PERF. (LOW TEMP.) = 1.86
3.45
OUTDOOR FAN POWER = 195 WATTS
3.54
INDOOR FAN POWER = 440 WATTS
3.64
NOTE: RATED WITH 25 FEET OF 7/8
3.73
SUCTION AND 3/8 LIQUID LINE
3.83
3.92
625
800
X0.99
X1.02
X1.01
X0.98
800
1025
X0.99
X1.02
X1.02
X0.98
875
1125
X0.99
X1.01
X1.02
X0.98
TWE5-PRC001-EN-10-15-99