Rfc 1628 Ups Mib; Mib - Liebert OpenComms Installation & User Manual

Network interface card
Table of Contents

Advertisement

provides the condition ID, the condition description, and the
condition time.

RFC 1628 UPS MIB

UPS units log alarms in the RFC 1628 UPS MIB. Traps for the
UPS units are generated out of the RFC 1628 UPS MIB. There
are four traps that may be sent for the UPS units: Trap On
Battery, Trap Test Completed, Trap Alarm Entry Added and
Trap Alarm Entry Removed.
The Trap on Battery is sent when the UPS is operating on battery
power. This trap will be sent once per minute until the UPS
either shuts down or is no longer running on battery power. This
trap pro-vides the Estimated Minutes Remaining on Battery, the
Seconds on Battery and the Configured Low Battery Time. The
Trap Test Completed is sent when a UPS diagnostic test is
completed. This trap provides the Test ID of the test that has
been performed, the Test Spin Lock, the Test Results Summary,
the Test Results Detail, the Test Start Time and the Test Elapsed
Time. The Trap Alarm Entry Added is sent when an alarm is
placed into the alarm table and provides the alarm ID and the
alarm description. This trap is not sent on the following alarms:
On Battery and Test In Progress.
Removed is sent when an alarm is removed from the alarm table
and provides the alarm ID and the alarm description. This trap is
not sent out when the Test In Progress alarm is removed from
the alarm table.

MIB

The Management Information Base (MIB) is a formal document
declaring the specifics of the information supported by the
SNMP implementation. The administrator for the NMS (or other
applications utilizing SNMP to communicate with the Liebert
units will need the MIB in order to integrate the Liebert units
into the monitoring system.