Operation Details - LG ABNW366KSA1 Service Manual

Ceiling duct type air conditioner
Hide thumbs Also See for ABNW366KSA1:
Table of Contents

Advertisement

Operation Details

Operation Details
(1) The function of main control
1. Time Delay safety Control
• 3min ... The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle.
(Protection of compressor)
• 30sec ... The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating
operation is OFF or switched to the other operation mode while compress is off.
While compressor is running, it takes 3~5 seconds to switch.
2. Soft-Dry Operation
• The indoor fan speed is automatically set to the low, so the shift of the indoor fan speed is impossible because of
already being set to the best speed for Dry Operation by Micom Control.
3. Cooling Mode Operation
• When selecting the Cooling(
troller and the operation diagram is as following.
Intake Air temp.
SET TEMP.+0.5°C
(COMP. ON)
SET TEMP. -0.5°C
(COMP. OFF)
INDOOR FAN
COMPRESSOR
24 Ceiling Duct type Air Conditioner
) Mode Operation, the unit will operate according to the setting by the remote con-
More than
3 minutes
Selecting
Low
fan speed
ON
OFF
More than
3 minutes
Selecting
Low
fan speed
ON
OFF
Selecting
fan speed
ON

Advertisement

Table of Contents
loading

Table of Contents