EDUS39-600-F2_a

2. Specifications

Slim Ceiling-Mounted Duct Type
Model
1
Cooling Capacity
2
Heating Capacity
Casing / Color
Dimensions: (H × W × D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Gas Pipes
Piping
Connections
Drain Pipe
Machine Weight (Mass)
5
Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25 ft / 7.5 m (Horizontal)
2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25 ft / 7.5 m (Horizontal)
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. The airflow is set to STANDARD before leaving the factory. You can switch between STANDARD ESP and HIGH ESP with the remote controller.
Refer to the fan curves for actual fan performance.
5. Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
6. Refer to page 10 for Power Input.
FXDQ-M
FXDQ07MVJU
Btu/h
7,500
Btu/h
8,500
Galvanized Steel Plate
7-7/8 × 27-9/16 × 24-7/16"
in (mm)
(200 x 698.5 x 622.3 mm)
2 × 12 × 17
ft² (m²)
1.36' (0.41 m)
Sirocco Fan
kW
0.06
cfm
280/226 (H/L)
4
in. Wg
0.12 - 0.04
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ1/4" / 6.4 mm (Flare Connection)
in / mm
φ1/2" / 12.7 mm (Flare Connection)
in / mm
VP20
in / mm
External Dia. 1-1/32" / 26.2 mm
Internal Dia. 25/32" / 19.8 mm
Lbs
51
dBA
33/29
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers, Conduit Mounting Plate,
Insulation Tube.
FXDQ09MVJU
9,500
10,500
Galvanized Steel Plate
7-7/8 × 27-9/16 × 24-7/16"
(200 x 698.5 x 622.3 mm)
2 × 12 × 17
1.36' (0.41 m)
Sirocco Fan
0.06
280/226 (H/L)
0.12 - 0.04
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ1/4" / 6.4 mm (Flare Connection)
φ1/2" / 12.7 mm (Flare Connection)
VP20
External Dia. 1-1/32" / 26.2 mm
Internal Dia. 25/32" / 19.8 mm
51
33/29
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers, Conduit Mounting Plate,
Insulation Tube.
C:3D051780A
Specifications
FXDQ12MVJU
12,000
13,500
Galvanized Steel Plate
7-7/8 × 27-9/16 × 24-7/16"
(200 x 698.5 x 622.3 mm)
3 × 12 × 17
1.36' (0.41 m)
Sirocco Fan
0.06
280/226 (H/L)
0.12 - 0.04
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ1/4" / 6.4 mm (Flare Connection)
φ1/2" / 12.7 mm (Flare Connection)
VP20
External Dia. 1-1/32" / 26.2 mm
Internal Dia. 25/32" / 19.8 mm
51
33/29
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation
Manual, Paper Pattern for Installation,
Drain Hose, Clamp Metal, Insulation for
Fitting, Sealing Pads, Clamps, Screws,
Washers, Conduit Mounting Plate,
Insulation Tube.
3