Daikin FXDQ-M Engineering Data page 5

R-410a slim ceiling mounted duct type
Hide thumbs Also See for FXDQ-M:
Table of Contents

Advertisement

Specifications
Slim Ceiling-Mounted Duct Type
Model
1
Cooling Capacity
2
Heating Capacity
Casing / Color
Dimensions: (H × W × D)
Rows × Stages × FPI
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output
Fan
Air Flow Rate (H/L)
External Static Pressure
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Air Filter
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
5
Sound Level (H/L)
Safety Devices
Refrigerant Control
Connectable outdoor unit
Standard Accessories
Drawing No.
Notes:
1. Nominal cooling capacities are based on the following conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
Equivalent ref. piping length: 25 ft / 7.5 m (Horizontal)
2. Nominal heating capacities are based on the following conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
Equivalent ref. piping length: 25 ft / 7.5 m (Horizontal)
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. The airflow is set to STANDARD before leaving the factory. You can switch between STANDARD ESP and HIGH ESP with the remote controller.
Refer to the fan curves for actual fan performance.
5. Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally somewhat higher as a result of installation conditions.
6. Refer to page 10 for Power Input.
4
Btu/h
Btu/h
Galvanized Steel Plate
in
7-7/8 × 35-7/16 × 24-7/16"
(mm)
(200 x 901.7 x 622.3 mm)
ft²
kW
cfm
4
in.Wg
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ1/4" / 6.4 mm (Flare Connection)
in / mm
φ1/2" / 12.7 mm (Flare Connection)
in / mm
External Dia. 1-1/32" / 26.2 mm
in / mm
Internal Dia. 25/32" / 19.8 mm
Lbs
dBA
Thermal Protector for Fan Motor
Electronic Expansion Valve
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Screws, Washers, Conduit Mounting
Plate, Insulation Tube.
FXDQ18MVJU
18,000
20,000
3 × 12 × 17
1.89'
Sirocco Fan
0.13
440/350 (H/L)
0.17 - 0.06
Direct Drive
63
35/31
Fuse,
R-410A Series
C:3D051780A
EDUS39-600-F2_a
FXDQ24MVJU
24,000
27,000
Galvanized Steel Plate
7-7/8 × 43-5/16 × 24-7/16"
(200 x 1100 x 622.3 mm)
3 × 12 × 17
2.44'
Sirocco Fan
0.13
580/460 (H/L)
0.17 - 0.06
Direct Drive
Microprocessor Thermostat
for Cooling and Heating
Foamed Polyethylene
Removal, Washable, Mildew Proof
φ3/8" / 9.5 mm (Flare Connection)
φ5/8" / 15.8 mm (Flare Connection)
External Dia. 1-1/32" / 26.2 mm
Internal Dia. 25/32" / 19.8 mm
71
36/32
Fuse,
Thermal Protector for Fan Motor
Electronic Expansion Valve
R-410A Series
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Screws, Washers, Conduit Mounting
Plate, Insulation Tube.
FXDQ-M

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents