Trane X1379088401 Installation, Operation And Maintenance Manual page 17

Programmable zone sensor
Table of Contents

Advertisement

Table 4.
Configuration options for sensors used with
Option
number
Function
Default temporary
14
override timer setting
Zone temperature
15
calibration
16
Default cooling setpoint
17
Default heating setpoint
18
Default supply air cool
19
Default supply air heat
20
Default warm-up
Minimum cooling
21
setpoint
Maximum heating
22
setpoint
23
Minimum supply air cool
Maximum supply air
24
heat
Maximum warm-up
25
time
Minimum setpoint
26
deadband
BAS-SVX17B-EN
variable-air-volume (VAV)
Option Value
1, 2, 3, 4, 5 (hours)
Displays current temperature
reading with any offsets:
• 1 = –9.9ºF (–5.5ºC)
• 100 = 0.0ºF (0.0ºC)
• 199 = 9.9ºF (9.9ºC)
45–98ºF (7.2–36.7ºC)
43–96ºF (6.1–35.6ºC)
40–80ºF (4.4–26.7ºC)
60–100ºF (15.6–37.8ºC)
50–90ºF (10–32.2º)
45–98ºF (7.2–36.7ºC)
43–96ºF (6.1–35.6ºC)
40–80ºF (4.4–26.7ºC)
60–160ºF (15.6–71.1ºC)
50–90ºF (10–32.2º)
0 = 2ºF (1ºC)
1 = 4ºF (2ºC)
2 = 5ºF (3ºC)
3 = 7ºF (4ºC)
4 = 8ºF (5ºC)
5 = 10ºF (6ºC)
units (continued)
Default
Description
3
Sets the default temporary override time in hours.
Allows for field calibration in 0.1ºF (0.6ºC) increments of
either the internal sensor on the sensor, or the remote
100
sensor if used.
(0
offset)
Important: Apply power to the sensor for 60 minutes before
calibrating.
If no setpoint has been programmed or the program is
74
lost, the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is
68
lost, the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is
55
lost, the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is
100
lost, the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is
68
lost, the value that is set becomes the operation setpoint.
Sets the minimum programmable cooling temperature
45
setpoint.
Sets the maximum programmable heating temperature
96
setpoint.
Sets the minimum programmable cooling temperature
40
setpoint.
Sets the maximum programmable heating temperature
160
setpoint.
Sets the maximum programmable heating temperature
90
setpoint.
Sets the minimum difference between the heating and
0
cooling setpoints.