Commercial Air Conditioning SERVICE MANUAL Models AD182AMERA AS182AVERA AU182AFERA Features High energy efficiency class-A Newly designed V-appearance for wall mounted unit Two optional control tpyes for duct type unit Can be connected with the universal outdoor unit AU182AFERA Infrared control type or wired control type...
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 1.DESCRIPTION OF PRODUCTS & FEATURES 1.1. Products code explanation S 18 Climate type: T1 (see table 1) Design number (R stands for design sequence, DC inverter frequency type) Product type: A stands for heat pump type, refrigerant is R22...
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 1.4 Product features Newly designed V- appearance indoor unit The wall mounted type indoor unit adopts the newly designed V appearance, more fashion, more beautiful. Adopt the much friendlier refrigerant R410a The air conditioner system adopts the greatly friendly refrigerant R410a, which is protective for the ozone layer and is good to avoid the earth getting warmer.
Page 5
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 1.5 New friendly refrigerant R410A introduction: ■R410A The working pressure of R410A is approximately 1.6 times higher than R22. Because the oil in the refrigerant is different, please do not mix them. Refrigerant...
Page 6
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA ■Piping material 1. Use the correct refrigerant piping and materials for R410A 2. For the pipe wall thickness, see the table below: Pipe diameter Φ6.35 Φ9.52 Φ12.7 Φ15.88 Φ19.1 Pipe wall thickness Note: Always observe and comply with the local regulations when installing the refrigerant piping.
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 2. SPECIFICATION item Model AU182AFERA/AS182AVERA Function cooling heating Capacity 5.1(1.8---6.0) 6.0(2.0---7.1) Sensible heat ratio 0.75 Total power input 1580(550---2650) 1650(600---2650) Max. power input 2650 2650 EER or COP 3.23 3.64 Dehumidifying capacity 10‐³×m³/h Power cable 4.0×3...
Page 8
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA AD182AMERA item Model cooling heating Function 5.1(1.8---6.0) 6.0(2.0---7.1) Capacity 0.75 Sensible heat ratio 1580(550---2650) 1650(600---2650) Total power input 2650 2650 Max. power input 3.23 3.64 EER or COP Dehumidifying capacity 10‐³×m³/h 4.0×3 Power cable...
Page 9
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA Norminal condition: indoor temperature (cooling): 27 ℃DB/19℃WB, indoor temperature (heating): 20℃DB Outdoor temperature(cooling): 35℃DB/24℃WB, outdoor temperature(heating): 7℃DB/6℃WB The noise level will be measured in the third octave band limited values, using a Real Time Analyser calibrated sound intensity meter.
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 3. Safety precaution Carefully read the following information in order to operate the airconditioner correctly. Below are listed three kinds of Safety Cautions and Suggestions. Incorrect operations may result in severe consequences of death or serious injuries.
Page 11
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA WARNING! Nothing or nobody is permitted to Installed electrical-leaking circuit placed on or stand on outdoor unit. breaker. It easily cause electrical shock without The falling of goods and people may circuit breaker.
Page 20
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -20-...
Page 21
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -21-...
Page 22
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -22-...
Page 23
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -23-...
Page 24
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA INSTRUCTIONS TO INSTALLATION Please read these "Safety Precautions" first then accurately execute the installation work. The precautionary points indicated herein are divided under two headings: WARNING and CAUTION those points which are related to the strong possibility of an...
Page 25
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA INSTRUCTIONS TO INSTALLATION PRECAUTION Execute proper grounding. Do not connect the earth wire to a gas pipe, water pipe, lightening rod, or a telephone ground wire. Improper placement of earth wires can result in electric shock.
Page 26
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA INSTRUCTIONS TO INSTALLATION WARNING BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE. BE SURE TO READ INSTALLATION MANUAL FOR INDOOR UNIT WITH THIS MANUAL.
Page 27
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA INSTALLATION PROCEDURE When the mounting plate is first fixed 1. Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
Page 28
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA INSTALLATION PROCEDURE Other direction piping Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according to the position of wall hole. When bending, be careful not to crash pipes.
Page 29
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA INSTALLATION PROCEDURE ELECTRICAL WIRING When connecting the cord before installing the indoor unit Insert the cord from the back side of the unit, then pull it out on the front side. Loosen the screws and insert the cord ends fully into terminal block, then tighten the screws.
Page 30
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA INSTALLATION CHECK AND TRIAL OPERATION Check the Layout of the Drain Pipe and Connection Wires The drain pipe should be placed underneath, and the connection wires should be placed upside; and the drain pipe especially the section inside the machine and indoors must be wound up with insulating material to preserve heat.
Page 31
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -31-...
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 6. Parts and Functions AD182AMERA AS182AVERA Air inlet grille Front panel Air inlet grille Louver Display board -32-...
Page 34
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -34-...
Page 35
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -35-...
Page 36
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -36-...
Page 37
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -37-...
Page 38
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -38-...
Page 39
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -39-...
Page 40
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -40-...
Page 41
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA LIGHT operation: The remote receiver of wall mounted unit is with the background lamp, press LIGHT button, according to the buzzer state, there are four modes of background lamp as follows: 1. Buzzer works, 5 seconds later, background lamp is off;...
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 7.2 Wired controller YR-E12 Buttons function: MODE:used for select indoor operation mode. FAN:used for select indoor air flow. SWING:used for setting indoor swing mode. HEALTH:used for setting indoor health function. TEMP + -:used for changing set temperature.
Page 43
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA [FAN] [HIGH]:high fan speed [FAN] [MED]: medium fan speed [FAN] [LOW]: low fan speed [FAN] [FIX]: fixed fan speed, it will display only when fixed fan speed is requested to main indoor unit.
Page 44
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA AUTO operation, COOLING, HEATING and DEHUMIDIFICATION operation 1) Start up operation: press the button of ON/OFF, the system will start up, and will display [MODE][AUTO];[FAN][AUTO];[ROOM TEMP.]+“24℃” ;[CLOCK]+”12:00”. 2) Select MODE: press the MODE button, then you will see in the display section [MODE] switch over in below sequence:[FAN ONLY]→[COOL]→[DRY]→[HEAT]→[AUTO]→[FAN...
Page 45
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA TIMER ON, press [TIMER]. [TIMER][ON] will be constant on. Then [TIMER] [OFF] flashes, press the clock +/- button to adjust the time of TIMER OFF, press [SET]. The time sequence of timer on and timer off will determine the mode is [TIMER] [ON] →[OFF] or [TIMER] [OFF] →[ON].
Page 46
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA CENTRAL control function When the central controller selects [CENTRAL] mode, the buttons in the wired controller except for [CHECK] will be invalid. VENTILATION mode (only for the unit with fresh air function or heat recovery...
Page 47
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA Preset ――― Outdoor total capacity Actual value, decimal In check mode, press [CHECK] to quit the check mode, and go into normal running mode. How to change the function switches? Type State of...
Page 48
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA There is no lock function only in the wired controller. But when it is connected with a central controller, if the central controller is set to “central”, the buttons in the wired controller will be invalid, or the buttons will be valid.
Page 49
sensor abnormal short circuit for more than 2m continuously Solenoid valve Solenoid valve ○ abnormal incorrectly times continuously Discharging temp. Sensor broken down or ○ sensor abnormal short circuit for more than 2m continuously EEPROM abnormal EEPROM data missing Run as the default value Pressure...
Page 50
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA If you use central control type, SW1, SW2 will be used simultaneously. Wiring request in central control type: port A-B is connected with indoor port CN16(A-B) through 2-core shield wire. Requirements: 1. Port A connects with port CN16(A)of all indoor units.
Page 51
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -51-...
Page 52
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -52-...
Page 53
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA -53-...
Page 54
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA Electrical functions of wired controller: 1.Function difference between master wired controller and slave one: Contrastive items Master wired controller Slave wired controller Function All of functions Only with below functions: ON/OFF, MODE, FAN SPEED, SET TEMP., SWING...
Page 55
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA connected with indoor unit is called master one, the other is called slave one. Master wired controller and indoor unit; master and slave wired controllers are all connected through 3 pieces of polar wire.
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 8. Electrical Control Functions 8.1. Outdoor electric control functions 8.1.1 Outdoor running frequency and the control procedure 8.1.1.1 Compressor startup Every time compressor is from OFF to ON, no matter how is the indoor target frequency, compressor running frequency must be stay at 40Hz and 60Hz for 1 minutes (At outdoor discharging temp.
Page 57
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA Below 28℃ Class-1 Class-3 Class-5 Compressor frequency F<25Hz 25Hz≤F<45Hz 45≤F in heating Over 15℃ Class-2 Class-4 Class-5 Below 15℃ Class-3 Class-5 Class-7 8.1.2.4 Outdoor fan speed control when selecting AC motor Selecting AC motor or DC motor depends on EEPROM.
Page 58
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA B. Defrost interval time When the value of C×TA-α is in the range of -15℃≤C×TA-α, two defrosting interval is 45 minutes. When the value of C×TA-α is in the range of C×TA-α<-15℃, two defrosting interval is 65 minutes.
Page 59
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 8.2. Additional functions 8.2.1 The interval between compressor stop to startup again is 3 minutes, which can protection compressor. If being electrified for the first time, compressor will start up only when the valve opens to the normal operation angle.
Page 60
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA R: rise at the speed of 1Hz/10s 8.2.4 Overcurrent protection(realised by power module) ●In the course of compressor startup, if current is over 21A and keeps for 4 seconds, compressor will stop and the unit alarms. 3 minutes later, compressor will re-start up, if in 10 minutes, it occurs for 3 times, the unit will stop and alarm.
Page 61
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA Put the first bit of dip switch on the indicator board at ON, the unit will enter compulsory cooling operation, as follow: Compressor Current, discharging Operation before minutes later after Manual adjustment startup...
Page 62
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA electrified after being powered off. Failure Emission Outdoor Failure description Corresponding outdoor CBD failure code code indicator display 00001 Power module IPM protection 00010 DC fan motor failure DC fan motor failure Communication Outodor alarms, not sends to indoor.
Page 63
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA Low pressure switch Low pressure switch acts for 30 seconds 11000 failure contineously Temperature cutoff protection 1)Indoor pipe temp. is abnormal, outdoor default cooling temp. : 5℃, heating temp.: 40℃. The above temperatures are normal.
Page 64
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA Wall mounted unit electric functions: 1. Temperature adjustment function 1.1 In this function, outdoor running frequency depends on the indoor temperature and the set temperature. 1.2 In auto mode, indoor fan speed will be changed according to the request of temperature adjustment.
Page 65
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA electrified for the first time, enter heating mode or defrosting is over, if heat exchanger temp. is below 25.2℃ and over 16℃, fan speed is ultra low; if heat exchanger temp. reduces below 23 ℃, fan motor speeds.).
Page 66
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 3.2 Power cooling operation 1) Modulate the set temperature. 2) Air flow is Manual High speed. 3) After compressor is running, in 3 minutes, the unit will not make low load protection. 3.3 Not available for Fan, Dry mode.
Page 67
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA Ts-2 Ts-3 Ts-4 7.3 Non-standard SLEEP function: the sleep function can realize 1~8 hours sleep mode when being combined with the TIMER function. 1) When in Auto mode, the unit will make SLEEP operation due to the setting.
Page 68
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA heat exchanger temp. THLHEATBL3 THLHEATBL2 THLHEATBL1 THLHEATBL0 Indication area normal area 2 area 1 stop area 1 area 2 normal In trial running, the low load protection is ignored. After compulsory cooling begins for 1 minute, for 3 minutes, the low load protection is cancelled temporarily.
Page 69
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 12. Temperature cutoff protection In cooling mode, every time compressor runs for 1 minute after startup, the unit will check the indoor coil temperature, when Tg>Tr+5, the unit will shut off for 3 minutes, and then re-start up;...
Page 70
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 15.2.2 Rated heating a. High speed at heating, the set temperature is 30℃, press temp. “+” and SET button simultaneously, after the buzzer sounds 2 times, enter the condition. b. In this condition, the unit will execute as follow: entering the rated frequency operation;...
Page 71
emergency operation as Auto mode. 17.2 In OFF state, press emergency switch for over 5 seconds and below 10 seconds contineously, the unit will begin trial running in cooling mode (30 minutes later quit the trial running). 17.3 In OFF state, press emergency switch for over 10 seconds and below 15 seconds contineously, the unit will show the previous failure.
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 10. Electric Wiring diagram T3.15A - 250VAC -72-...
Page 73
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA New PCB 0010452040 CN27 CN26 CN25 CN10 CN19 CN11 CN12 CN13 CN14 CN16 CN15 CN17 CN21 New filter board 0010403645 -73-...
Page 74
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA AS182AVERA: WIRING DIAGRAM OF WALL MOUNTED UNIT 0010576611 SWING SWING SWING SWING MOTOR 1 MOTOR 2 MOTOR 3 MOTOR 4 RECEIVER PIPING TEMP. SENSOR NEGATIVE ION GENERATOR R-MOTOR L-MOTOR UP DOWN CON3 ROOM TEMP.
Page 75
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA AD182AMERA: CIRCUIT DIAGRAM OF INDOOR UNIT 0010576546 FUSE T2.0A/250VAC REMOTE REMOTE W:WHITE B:BLACK CENTRALIZED RECEIVER R:RED Y:YELLOW CONTROLLER OR:ORANGE BL:BLUE TRANS. BR:BROWN FG L Y/G:YELLOW/GREEN TRANS.:TRANSFORMER FILTER MOTOR CN12 (ALARM) CN14 CN16 CN17...
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 12. Troubleshooting Outdoor troubleshooting: B elow the indication on indicator board sequence is LE D 5-LE D 4-LE D 3-LE D 2-LE D 1, 0: O FF; 1: O N 1 ) S ensor failure A larm condition: am bient tem perature sen sor is in short circuit or open circuit for 3 seconds con tinously.
Page 81
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 3) Outdoor DC motor abnormal Outdoor indicator displays 00010. Alarm condition:outdoor DC motor is blocked rotor or broken, abnormal. This fault is only used when indoor unit is with DC fan motor. outdoor indicator shows 00010...
Page 82
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA For convertible unit and ceiling concealed unit: compressor can not startup after unit is switched on for 4 minutes if indoor unit alarms other eliminate other failure codes faults check if wiring between indoor...
Page 83
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 6) Outdoor SPDU module over current protection Outdoor indicator shows 00101. Alarm condition: When compressor running, the module current is over 21A. outdoor failure indicator shows 00101 check if the refrigerant is adjust refrigerant...
Page 84
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 9) EEPROM is abnormal Outdoor indicator shows 01110. Alarm condition: EEPROM is fault or data is missing. outdoor indicator shows 01110 check if EEPROM welded points adjust EEPROM on outdoor PCB is in good...
Page 85
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 12) Outdoor low pressure abnormal Outdoor indicator shows 11000. Alarm condition: outdoor system pressure is lower than 0.05MPa. outdoor indicator shows 11000 measure actual pressure by a replace pressure pressure gauge to adjust the...
Page 86
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 2) EEPROM failure Alarm condition: before being electrified, EEPROM is faulty or the data is missing. outdoor failure indicator shows 01110 check the EEPROM modify the welded point on outdoor welded point PCB is normal...
Page 87
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 4) Indoor DC motor abnormal Alarm condition:outdoor DC motor is blocked rotor or broken, abnormal. This fault is only used when indoor unit is with DC fan motor. LCD of wall mounted unit display F2...
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA 15. Air velocity distribution AD182AMERA: cooling air discharge angle 5 Air Velocity distribution cooling air discharge angle 5 Temperature distribution heating air discharge angle 45 Air Velocity distribution -96-...
Page 96
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA heating air discharge angle 45 Temperature distribution -97-...
Page 97
Commercial Air Conditioner Model: AU182AFERA AD182AMERA, AS182AVERA AS182AVERA air velocity distribution: unit m/s Fig 1 top view flow control panel horizal 0.25 lourer:center unit m/s 0.5 0.25 Fig 2 top view flow control panel horizontal lourer:right and left 0.25 unit m/s...
Page 98