Haier AD182AMERA Service Manual page 68

Commercial air conditioning
Hide thumbs Also See for AD182AMERA:
Table of Contents

Advertisement

heat exchanger temp.
THLHEATBL3
THLHEATBL2
THLHEATBL1
THLHEATBL0
Indication area
In trial running, the low load protection is ignored.
After compulsory cooling begins for 1 minute, for 3 minutes, the low load protection is cancelled
temporarily. (THLH[3,2,1,0]= 7℃ ,4.6℃,2.2℃,-0.5℃)
11. High load protection
In heating mode, make high load protection due to the heat exchanger temperature.
heat exchanger temp.
THHEAT6
74.7
THHEAT5
70.3
THHEAT4
65.1
THHEAT3
62.2
THHEAT2
52.9
THHEAT1
51.6
THHEAT0
47.1
Indication FQY
normal
When the heat exchanger temperature is not up to "THHEAT[2]", the temperature will resume
the control of normal temperature area.
Temp. point
Temp.
THHEAT3
62.6
THHEAT4
65.1
THHEAT5
70.3
THHEAT6
74.4
Commercial Air Conditioner
normal
area 2
area 1
frequency when high load protection begins
C D E
standby
High load protection
FQY point
FQHHEAT2
FQHHEAT3
FQHHEAT4
Stop
stop
area 1
D
C B
A
FQY
70
40
30
-68-
Model: AU182AFERA
AD182AMERA, AS182AVERA
area 2
normal
B
C D E
stop