Note: "1" :dip switch at ON, "0": dip switch at OFF.
2. Sign definition:
Indoor
Tai
Tc1
Tc2
Outlet
Inlet
Ambient
pipe
pipe
temp.
temp.
temp.
Tcomp1,2
Temp. compensation
3. Dry operation
Tai<16℃, indoor unit stops running and sends stop-unit signal to outdoor.
Tai≤Tset, indoor motor runs at low speed and sends stop-unit signal to outdoor.
4. Fan operation
Indoor fan motor will run as the fan speed set on the remote controller or the wired controller and indoor
unit will send the stop-unit signal to outdoor.
5. Auto operation
5.1 If the unit enters Auto mode for the first time, the system will adjust the operation mode according to
the room temp. and the set temp.
When Tai≥Tset, entering auto cooling mode;
When Tai<Tset, entering auto heating mode.
5.2 Auto cooling mode is as the same as the cooling mode. After the thermostat is OFF for 15 minutes, if
Tai+ 1+Tcomp2<Tset, the unit will enter auto heating mode, or the unit will still stay at auto cooling mode
and stop when it reaches the set temperature; while the indoor motor will be at low speed.
5.3 Auto heating mode is as the same as the heating mode. After the thermostat is OFF for 15 minutes, if
Tai≥Tset+1 +Tcomp1, the unit will enter auto cooling mode, or the unit will still stay at auto heating mode;
5.4 In this mode, the Sleep function is available, run as cooling sleep in cooling mode and as heating
sleep in heating mode. Once sleep mode is set, the mode will not change after the unit stops for 15
minutes when it arrives Tset.
5.5 Mode conversion will be confirmed after compressor has stopped for 10 minutes.
6. Abnormal operation
6.1 When outdoor modes from the request of indoor unit conflict, the one entering firstly will take priority.
Commercial Air Conditioner
0
1
0
Indoor communication address 3
0
1
1
Indoor communication address 4
1
0
0
Indoor communication address 5
1
0
1
Indoor communication address 6
1
1
0
Indoor communication address 7
1
1
1
Indoor communication address 8
Tm
Tao
Toci
mid
Thick pipe
Ambient
coil
of heat
temp.
temp.
exchanger
Tset
Set
temp.
-26-
Model: AD09/12/14/182XLERA
outdoor
Tc
Te
Ts
mid
Compressor
Defrost
condenser
suction
temp.
temp.
temp.
Td
Compressor
discharging
temp.