The connection pipes shall also be wound up with insulating material to preserve
the temperature. The airing direction shall be from bottom to top.
Wiring methods:
1 Wiring method of ring terminal
For connecting line which end is a ring,its wiring method as shown in the right figure: remove wiring screw and
pass it through the end ring of connecting line,then connect it to the terminal block and tighten screw.
B=8.0-9.0(mm)
d=4.3-5.3(mm)
T=1.0-2.0(mm)
(For your reference)
2 Wiring method of straight terminal
For connecting line whose end is not a ring, its wiring method as follows: loosen wiring screw and insert the end
of connecting line totally into the terminal block,then tighten the screw and pull the connecting line slightly to
confirm that it is clamped firmly.
3 Crimp connection method of connecting line
After finishing wiring.connecting line must be fastened by wire clamp,which is pressed on the external sheath of
the connecting line, as shown in the figure:
Commercial Air Conditioner
NOTE!
Brazed seam
Ring Terminal
Incorrect crimp
Correct crimp
connection of wire
connection of wire
Terminal block
Crimp connection
clamp
-17-