RHA36B2A
Remote Heat Pump
Specifications
Cooling Capacity, BTUH (Nominal)
Compressor
R.L. Amps
L.R. Amps
Condenser Fan Motor
Horsepower
R.L. Amps
L.R. Amps
Liquid Line, Inches O.D.
Suction Line, Inches O.D.
Refrigerant Charge (oz)
Power Supply
Min Circuit Ampacity
Max Overcurrent Device
Electric Conduit Size (in)
Power Supply
Low Voltage
Approximate Shipping Weight (Lbs)
NOTE: It is important to electrically connect the unit and
properly size fuses/circuit breakers and wires in accor-
dance with all national and/or local electrical codes. Use
copper wire only.
Heat Pump Performance Data
For ARI Performance Data: See the ARI Directory, Product Data Booklet (PDB), or the product Service Manual.
65
60
T
34
32
Amps
17.0 15.8 14.8 13.9 13.4 13.2 12.4 11.8 11.3 10.8 10.3 10.1
HI PR
267
256
LO PR
74
68
Above information is for nominal CFM and 70° F indoor dry bulb.
All pressures are PSIG. All temperatures are °F.
Amps are outdoor unit amps.
Low pressure is measured at the gauge port. High pressure is measured at the liquid service valve.
May 1998
Heating Air Conditioning
36,000
15.7
93.0
1/4
1.7
3.3
3/8
3/4
144
208/230-60-1
22.1
35
1/2 or 3/4
1/2
170
RHA36B2A / BBA36A2A / CCA42FCC
Outdoor Ambient Temperature (° F)
55
50
47
45
40
30
28
27
26
24
246
236
230
226
217
64
59
56
53
49
Amana
Fayetteville, TN 37334
®
Specification Sheet
Due to policy of continual product improvement, the right
is reserved to change specifications and design without
notice.
Standard Features
• Bi-Flow Liquid Line Drier (Shipped Loose)
• Front Seating Valves
• Time-Temperature Defrost System
• Low RPM (825) Condenser Fan
• 5 Minute Anti-Short Cycle Protection
• Scroll Compressor
• Accumulator
Accessories
• Pressure Control Kit (PCK03A)
Automatic High Pressure Switch
Time Delay
• Fossil Fuel Kit (FFK03A)
• Compressor Sound Blanket (CSB07A)
• Ambient Temperature Kit (ATK05)
• Low Ambient Control (LAC03A)
When mix matching with restrictor orifice indoor coil, use
restrictor orifice part number B1443808, 0.069" diameter
or 11076306, 0.0689" diameter.
NOTE: Defrost control compressor run time is factory set
at 90 minutes.
35
30
25
20
17
22
21
19
18
17
208
199
191
183
179
44
39
35
31
29
15
10
5
0
-5
16
14
13
11
10
9.9
9.4
8.8
8.3
7.7
175
169
162
156
150
28
23
20
17
15
-10
8
6.9
145
12
20209804

Advertisement

loading

Summary of Contents for Amana RHA36B2A

  • Page 1 Heat Pump Performance Data For ARI Performance Data: See the ARI Directory, Product Data Booklet (PDB), or the product Service Manual. RHA36B2A / BBA36A2A / CCA42FCC Outdoor Ambient Temperature (° F) Amps 17.0 15.8 14.8 13.9 13.4 13.2 12.4 11.8 11.3 10.8 10.3 10.1...
  • Page 2 RHA36B2A / BBA36A2A / CCA42FCC Outdoor Ambient Temperature (F°) Entering Indoor Wet Bulb Temperature IDB* Airflow Delta T 1350 AMPS 10.8 11.0 11.4 11.6 11.9 12.3 12.6 12.9 13.3 13.4 13.7 14.2 14.3 14.6 15.1 15.1 15.5 16.0 HI PR...