Configuration as Shared Device
"IM153-4 PN ST as of V3.0 Shared Device" or "IM153-4 PN HF as of V3.0 Shared Device"
must be used for the configuration of shared device. The remaining configuration is done in
the usual way.
When configuring as a Shared Device, the OB 83 must be integrated into the block list,
because the transition from STOP to RUN will generate so-called "Return of submodule"
alarms. The alarms are intercepted by the OB 83, otherwise the CPU would go into STOP.
Both IO controllers that share the device must be in "RUN" in order for the IM 153-4 PN to be
able to send data to the I/O.
See also STEP 7 documentation
(http://support.automation.siemens.com/WW/view/en/10805384/133300).
Isochronous real-time communication
Synchronized communication protocol for cyclic exchange of IRT data between PROFINET
devices. A reserved bandwidth within the send clock is available for the IRT data. The
reserved bandwidth ensures that the IRT data can be transmitted at reserved, synchronized
intervals while remaining uninfluenced by another greater network load (for example, TCP/IP
communication or additional real time communication).
The IRT option "high flexibility" permits simple planning and expansion of the system.
Topological configuration is not required.
The "high performance" IRT option requires a configuration of the topology.
Note
IO controller as a sync master for IRT communication with the option "high performance"
We recommend also operating the IO controller as a Sync-Master if you configure the IRT
communication with the option "high performance".
Otherwise, IRT and RT configured IO devices may fail if the sync master fails.
You can find additional information about configuring synchronized PROFINET devices in
Sync domains in the STEP 7 online help and in the PROFINET system description
(http://support.automation.siemens.com/WW/view/en/19292127) manual.
Fail-safe signal modules (only 6ES7153-4BA00-0XB0)
The following fail-safe signal modules can be used with the 6ES7153-4BA00-0XB0 interface
module:
Module
SM 326; DI 24 x DC 24V
SM 336; F-AI 6 x 0/4 ... 20 mA HART
SM 326; F-DO 10 x DC 24V/2A PP
SM 326; DO 8 x DC 24V/2A PM
A safety protector is
Interface modules IM 153-4 PN and IM 153-2 HF
Product Information, 12/2013, A5E02714952-04
Order no.
6ES7326-1BK02-0AB0
6ES7336-4GE00-0AB0
6ES7326-2BF10-0AB0
6ES7326-2BF41-0AB0
no
longer required for these modules.
Product information
2.2 The new functions for the IM 153-4
As of product
version
1
1
1
1
11