GENERATOR VOLTAGE ADJUSTMENT
,
NOTE: WESTERBEKE recommends that the following generator
tests and adjustments be peiformed
by
a quailified technician.
Generator Frequency
1. Frequency is a direct result of engine/generator speed:
1800 rpm
=
60 hertz
1500 rpm
=
50 hertz.
d. After the no-load hertz adjustment is made, the no-load
voltage may need to be readjusted. In most cases, if the
generator was producing the correct no-load voltage at
the previous hertz setting, it would be correct at the
changed hertz setting.
2. To change generator frequency follow the steps below.
a.
Connect the AC output leads to the AC terminal block,
following the illustrations on this page.
h.
If an AVR is installed, reposition the blue or blue/white
lead to correspond to the hertz selected on the
Voltage!Hertz Connection Bar.
If there is no automatic voltage regulator (AVR
installed, do not change the wiring on the
Voltage/Hertz Connection Bar. Simply reconfigure the
AC terminal for the hertz change.
c. Start the engine, monitor voltage and adjust engine
no-load speed. Adjust diesel units by the linkage
between the throttle arm and fuel soienoid or the
throttle lever on the injection pump ..
60 hertz
no-load speed
60.0 -
60.5 hertz
50 hertz
no-load speed
50.0 - 50.5 hertz
In the event it needs adjustment, adjust the shim thick-
ness under the laminated steel bar of the transformer.
60 hertz:
no-load voltage, 121-124 volts.
50 hertz:
no-load voltage, 232-236 volts.
e. Load the generator to the rated amperage output
corresponding to the hertz speed of the generator.
Rated Loaded Speed
60 hertz
loaded speed
59.5 - 60.0 hertz
50 hertz
loaded speed
49.5 - 50.0 hertz
The lowest acceptable voltage at full rated output
(amps)
60 hertz:
108 - 110 volts
50
h~rtz:
205 - 210 volts
SIX STUD AC VOLTAGE CONNECTIONS
115V 50Hz
®
@
The frame ground wire must
be moved when changing
from 115 volts and 1101220
volts 50 hem to 230 volts
50 hertz. From making con-
nections to the AC terminal
115V 50Hz
block.
use
terminal ends for
'!H-<I::::]
1/4 inch studs that will
accept
multi-strand
copper
wire sized for the amperage
rating from the hot lead con-
nection. The frame ground
wire is white or white with a
green strip. It connects
between the neutral stud
and the generator frame.
230VSOHz
@
120V 60HZ
A JUMPER IS
PfiiL-J
REQUIRED:-' ~~!iJ
TWELVE STUD AC VOLTAGE CONNECTIONS
CIRCUIT
BREAKER
230V50Hz
N L1
I (
115/230V 50Hz
a:::::o
0
L1
L2
• •
Engines & Generators
40
120V60 Hz
N
\ JUMPER IS
REQUIRED
120/240V 60HZ
120/240V/60Hz
L1
L2