GENERATOR AC VOLTAGE CONNECTIONS
AC VOLTAGE CONNECTIONS
The frame ground wire (green) must be properly positioned
when changing the AC output configuration of the AC
terminal block. For making connections to the AC terminal
block, use terminal ends for l/4 inch studs that will accept
multi strand copper wire sized for the amperage rating from
the hot lead connection. The frame ground green wire
connects between the neutral stud and the generator frame.
Generator Frequency
I. Frequency is a direct result of engine/generator speed:
1800 rpm = 60 hertz; 1500 rmp = 50 hertz.
2. To change generator frequency, follow the steps below:
120/240V
60Hz
230V 50Hz
r-:;;:"...,..-=-,
U 1
120V 60Hz
NOTE: When changing from 60 Hz
to 60 Hz see operator·. manual.
Configure the AC terminal block for the desired voltage
frequency as shown. Ensure that the case ground wire is
connected to the correct terminal block neutral ground
stud.
Check
Hz
jumper on AC voltage
regulator.
3. Remove or install the jumper on the automatic regulator
(depending on frequency). Refer to BE GENERATOR.
NOTE:
The green ground wire may be removed in those
installations where the AC circuit has a separate neutral
and ground circuit. This will prevent the unit from being
a ground source in the vessel.
!V\T/WESTERBEKE
I
CONNECTq
FOR 50Hz
,-- - - - - - - - - - - - - - - - - GENERATOR - - - - --- - - - - -
~
iEXCITERr- - - - --ROTOR- --1 , - ------STATOR·-i
!
ISTATOR
I
I :
AC OUTPUT WINDINGS 2
I
I
I
I
81
11
'
I
+
:1
I
~
II
II
l------f.-_,~~~
.
AC
OUTPUT WINDINGS 1
I
I
1
V12
~
__________ J:
_____
'-_-_-_-_-_-_-..J-+--"'t
j
-V11
________________ 1
POTENTIOMETER
46455
AUTOMATIC
VOLTAGE
REGULATOR
Hz
Hz
VAR
~
VOlTAGE
o
FOR EXTERNAL
c::
VAR
F-
ADJUSTMENT
F2
(WHITE)
GENERATOR INTERNAL WIRING DIAGRAM
'------+U1
'------+U2
F1 (RED)
AVR CONNECTIONS
~
,...,
60 Hz - 120/240V_ U1
V11
60 Hz -120V _ _ U1
V11
50 Hz .. 230V ___ U1'\ V12
F+
" - '
,..,.,
WIRE COLOR CODE
A VR CONNECTIONS (September 2004 Production on)
T2 YELLOW
60Hz
T3
ORANGE
60Hz
T4 LT.
GREEN
TS LT.
RED
50Hz
Engines
&
Generators
41
120/240V
l20V
230V
..........,. r.-
T2 : T4
T3
T5
T2
T4