OPERATING PROCEDURE
6. Removing the compressor and 4-way valve
(1) Remove the top panel, cabinet and service panel.
(Refer to 1.)
(2) Remove the back panel. (Refer to 1.)
(3) Remove the inverter assembly. (Refer to 2.)
(4) Recover gas from the refrigerant circuit.
Recover gas from the pipes until the pressure
NOTE:
gauge shows 0 kg/cm
(5) Detach the welded part of the suction and the discharge
pipe connected with compressor. (Photo 11)
(6) Remove the compressor nuts.
(7) Remove the compressor.
(8) Detach the welded part of 4-way valve and pipe. (Photo 10)
7. Removing the reactor
(1) Remove the top panel. (Refer to 1.)
(2) Disconnect the reactor lead wire.
(3) Remove the screws of the reactor, and remove the reactor.
(0 MPa).
2
69
PHOTOS
Photo 10
Welded parts of 4-way valve
Photo 11
Photo 12
Screws of the reactor
R.V. coil
Welded part
of the dis-
charge pipe
Welded part
of the suction
pipe