3 | F220 Photoelectric Smoke Detectors
Loop Supervision
Loop supervision requires one D275 or F220-B6E per
loop when using F220‑B6R/B6C bases and is
supervised by the control panel.
Wiring the Bases
Refer to the F220 Series Detectors with
F220‑B6/C/E/R Bases Installation Instructions
(P/N: 4998138694), the F220 Series Detectors with
F220‑B6RS Bases Installation Instructions
(P/N: F01U029847), or the F220-B6PS/M Installation
Instructions (P/N: 4998149982) for detailed wiring
instructions.
Technical specifications
Environmental Considerations
Relative Humidity:
0% to 95% non-condensing;
15% to 95% non-condensing for CO sensing
model
Temperature
+32°F to +100°F (0°C to +38°C)
(normal operating):
Mechanical Properties
Color:
Dimensions (diameter x H):
Power Requirements
Current (alarm):
20 mA minimum at 8.5 VDC;
(detector head only)
35 mA maximum at 32 VDC
Current (start-Up):
0.12 mA maximum at 32 VDC
Maximum RMS Ripple:
25% of DC input
Power-up Time:
22 seconds maximum
Voltage (standby)
F220-B6:
8.5 VDC to 32.0 VDC
F220-B6C/-B6R/-B6E:
10.0 VDC to 30.0 VDC
F220-B6RS:
16.0 VDC to 30.0 VDC
F220-B6PM:
with D299: 18.9 VDC to 28.0 VDC
without D299: 9.6 VDC to 28.0 VDC
F220- B6PS:
18.9 VDC to 28.0 VDC
Trademarks
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.
Ordering information
F220‑PTHC Photoelectric Smoke Detector with +135°F
(+57°C) Heat and Carbon Monoxide Sensors
Photoelectric detector head with heat and CO sensor
augmentation only; requires base.
Order number
F220-PTHC
White
6.75 in. x 2.25 in.
(17.1 cm x 6.4 cm)
F220‑PTH Photoelectric Smoke Detector with +135°F
(+57°C) Heat Sensor
Photoelectric detector head with heat sensor only;
requires base.
Order number
F220-PTH
F220‑P Photoelectric Smoke Detector
Photoelectric detector head only; requires base.
Order number
F220-P
Accessories
D275 Power Supervision Module
Line supervision device for four-wire fire detection
circuits
Order number
D275
DRA‑5 Remote Annunciator (5 VDC)
Designed to provide remote annunciation of alarms for
a number of Bosch smoke and heat detectors
Order number
DRA-5
DT‑2 Detector Removal Tool
Use the DT‑2 to remove, replace, or test the detector
head
Order number
DT-2
F220‑B6 12/24 VDC Two‑wire Base
Standard base for two‑wire (12 VDC or 24 VDC
system) applications.
Order number
F220-B6
F220‑B6R Standard 12/24 VDC Four‑wire Base
Standard base for four‑wire (12 VDC or 24 VDC)
detector systems.
Order number
F220-B6R
F220‑B6RS 24 VDC Four‑wire Detector Base with Soun-
der
Four-wire detector base with sounder for use with the
F220 Series Photoelectric Smoke and Heat Detectors.
Order number
F220-B6RS
F220‑B6C 12/24 VDC Four‑wire Base with Auxiliary
Form C Relay
Four‑wire base with a normally‑open (NO) alarm loop
relay and a set of auxiliary contacts (Form C).
Order number
F220-B6C
F220‑B6E 12/24 VDC Four‑wire Power Supervision Base
with End‑of‑line Power Monitoring Relay
Four‑wire base with a normally‑open (NO) alarm relay
and an EOL power supervision relay.
Order number
F220-B6E
F220‑B6PM 24 VDC Four‑wire Addressable Master De-
tector Base
The Master base provides an address on the FACP
data expansion circuit for its detector and up to an
additional 19 detectors. It accepts the F220
Photoelectric Smoke Detector Heads and Heat
Detector Heads.
Order number
F220-B6PM