7. .13Fan Motor(DC Motor) or Related Abnormality
LED1 flash 9 times
The rotation speed detected by the Hall IC during fan motor operation is used to
abnormal fan motor operation
when the detected rotation feedback singal don't receiced in 2 minutes
1. Check connector connection.
2. Check motor power supply voltage output (pins 4-7).
3. Check motor control voltage (pins 4-3).
4. Check rotation command voltage output (pins 4-1).
5. Check rotation pulse input (pins 4-2).
Notes:the a/c is electrifying,don't pull out or insert the terminals of
the motor,else the motor would be damaged
HSU09VHJ DB -SM
Operation halt due to short circuit inside the fan motor winding.
Operation halt due to breaking of wire inside the fan motor .
Operation halt due to breaking of the fan motor lead wires
Dedection error due to faulty indoor unit PCB
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.