CAUTION
• When clamping wiring, use the included clamping material to prevent outside pressure being exerted on the
wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and does not
cause the control box lid to stick up, then close the cover firmly.
• When attaching the control box lid, make sure you do not pinch any wires.
• After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (pro-
cured locally) to prevent small animals and insects from entering the unit from outside. (If they get in, they
could cause short circuits in the control box.)
• Outside the unit, separate the low voltage wiring (remote controller cord) and high voltage wiring (power
supply, ground, and other power wiring) at least 2in. so that they do not pass through the same place
together. Proximity may cause electrical interference, malfunctions, and breakage.
Remote controller wiring
Putty or thermal insulation material
(procured locally)
9-2 Wiring example
• Fit the power supply wiring of each unit with a switch and fuse as shown in the drawing.
COMPLETE SYSTEM EXAMPLE (3 systems)
Power supply
Main
switch
20
Processing method of wiring through-holes
Sealing pad (Small) (13)
BS unit
(Only for
Heat
recovery system)
Indoor unit
Remote controller
Wiring through-holes
Power supply wiring
Transmission wiring
Switch
Fuse
Fig. 28