Table 47 Cutting Failsafe Direction Jumper - Honeywell ST 3000 User Manual

Smart transmitter release 300 and smart field communicator model sts103
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

8.3
Changing Default Failsafe Direction,
Procedure, continued
Figure 49
Location of Failsafe Direction Jumper on PWA.
Failsafe
Direction
Jumper
6/05
ST 3000 Release 300 and SFC Model STS103 User's Manual
Table 47
Cutting Failsafe Direction Jumper
Step
Turn OFF transmitter power. Loosen end-cap lock and unscrew end
1
cap from electronics side of transmitter housing.
If applicable, carefully turn Local Smart Meter counterclockwise to
2
remove it from PWA mounting bracket and unplug cable from
connector on back of meter assembly.
Loosen two retaining screws and carefully pull mounting bracket and
PWA from housing. Unplug flex tape and power connectors from
component side of PWA, and remove PWA.
With component side of PWA facing you, locate failsafe direction
3
jumper W1 and cut it in half with small wire cutter such as dykes. See
Figure 48. This changes failsafe action from upscale to downscale.
4
Reverse applicable previous steps to replace PWA.
Turn ON transmitter power.
5
Continued
Action
Power
Connector
Meter
Connector
157