Direct Vent Diagram - State Water Heaters she50 Instruction Manual

She50 100 series commercial gas water heaters
Table of Contents

Advertisement

fIGure 29.
fIGure 31.
When direct venting through the wall, as shown in Figure 33, the
exhaust should terminate a minimum of 24" from the air intake. The
exhaust may be rotated up to 45 degrees left or right as long as the
24" distance is maintained.
The air intake screen can be removed for space heating at cold climate
installation to prevent potential air intake freeze up. If air intake screen
is removed during winter to prevent freezing it is recommended to re-
install the screen during non-space heating seasons.
If necessary to achieve the 12" minimum clearance above the highest
anticipated snow level or grade for the air intake install a snorkel,
similar to the exhaust, in the up position. Maintain the 24" distance
between the intake and exhaust terminations.
Optional cold climate sidewall direct vent kits are available: 318221-
000 for 2" vent systems and 318222-000 for 3" vent systems.

dIrect vent dIaGraM

12" MINIMUM CLEARANCE ABOVE HIGHEST
ANTICIPATED SNOW LEVEL
24" MINIMUM SEPARATION. EXHAUST
MUST BE AT SAME LEVEL OR ABOVE
INTAKE TERMINAL.
30
fIGure 30.
fIGure 32.
fIGure 33.
12" MINIMUM CLEARANCE
ABOVE HIGHEST ANTICIPATED
SNOW LEVEL

Advertisement

Table of Contents
loading

This manual is also suitable for:

She100She50 124She50 125

Table of Contents