Location And Clearances - ICP H9MPT050F12B1 Installation Instructions Manual

90+2-stage &*9mpt & *9mpv variable speed
Table of Contents

Advertisement

2.
When y oureturn h ome, your f urnace will b eready t ostart, asitis
notnecessary todrain theantifreeze from thefurnace•
Disconnect the3/4" O Drubber hose from thecondensate
trap.Insert a funnel i ntothehose andandpour f our(4)
ounces o fsanitary t ype(RV) antifreeze intotheplastic
Transition box.Squeeze thehose together near t heend
and quickly r econnect
the
3/4" OD rubber
hose to the stub
on the condensate
trap. Secure
with the hose clamp•
2. Installation
Poison carbon monoxide gas Hazard.
This furnace can NOT be common vented or connected
to any type B, BW or L vent or vent connector, nor to
any portion of a factory-built
or masonry chimney. If
this furnace is replacing a previously common-vented
furnace, it may be necessary to resize the existing vent
and chimney to prevent oversizing
problems for the
other
remaining
appliance(s).
See
Venting
and
Combustion Air Check in Gas Vent lnstallation section.
This furnace MUST be vented to the outside.
Failure
to
properly
vent
this
furnace
or
other
appliances can result in death, personal injury and/or
property damage.
Locationand Clearances
1.
Refer
to Figure
1 or Figure
2 for typical
installation
and
basic connecting
parts required.
Refer to Figure
4 for typi-
cal horizontal
direct vent installation
and basic connecting
parts required.
Supply
and return air plenums
and duct are
also required.
2.
If furnace
is a replacement,
it is usually
best to install the
furnace
where
the old one was.
Choose
the location
or
evaluate
the existing
location
based
upon
the minimum
clearance
and furnace
dimensions
(Figure
3).
CAUTION
Special precautions MUST be made if installing furnace in an
area which
may drop below freezing.
This
can cause
improper
operation
or damage
to equipment.
If furnace
environment has the potential of freezing, the drain trap and
drainline must be protected. The use of electric heat tape or
RV antifreeze is recommended
for these installations.
(See
"Condensate
Trap Freeze Protection
Section")
Do NOT
operate
furnace
in a corrosive
atmosphere
containing
chlorine,
fluorine
or
any
other
damaging
chemicals.
Refer to Combustion
& Ventilation Air section,
Contaminated
Combustion Air.
Typical
Upflow
Installation
AIuminum or non-rusting s hield recommended.
(See Vent T ermination S hielding f ordimensions).
*8" Min.
20' Max.
[_
_lnlet
Pipe
insame
_
_(notusedon
atmoepheris(_ _
SinglePipe
model)
I
Vent PipesMUST
supported
Horizontallyand
Vertically
Coupling
on
ends of exhauel
pipe.Totalpipe&
cou_lJJ:Lq..outside
31' Min.
01Max.
I
same
atmo-
I_heric
zolle
*
H
i,
Increaseminimumfrom8to18 forcoldclimates(sustainedtemperatures
below 0o F).
25-23-33
iiiil;iii!i
¸iiiill ¸!;;;;i;il;ii;il;iiil;i;il;;i;iiii;iiiii
¸ii!!!;;;ii;;;;;;;;;;;;;;iiiii
¸iiiiii
iiiiiiiiiiiiii!il
Typical Downflow Installation
SeeVentTermination
Shielding in
Vent
Coupling on in-
Section.
side and outside
• _
1_'8"
Min.
Inlet Pipe
_
_]
20' Max
(notused on
U
'
SngePpe_
_
In same
model)
,:_ d=b
atmospheric
zone
e MUSTb
supportedHorizot
tally andVerticall I
Min.
Max.
same
* Increase minimumfrom 8" to 18" for cold climates(sustained
temperatures below0°F).
25-23-33a
440 01 201202
E_

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the H9MPT050F12B1 and is the answer not in the manual?

Table of Contents