Refrigerant; Refrigerant Piping Work - Mitsubishi Electric Mr. SLim SEZ-KD09NA Installation Manual

Air conditioners
Hide thumbs Also See for Mr. SLim SEZ-KD09NA:
Table of Contents

Advertisement

Available languages

Available languages

6. Refrigerant
piping work
6.1. Refrigerant pipe
[Fig. 6-1] (P.3)
Ca_ I ndoor unit
@ Outdoor unit
Refer to the outdoor unit Instruction
Manual for restrictions on
the height difference
between
units and for the amount of additional
refrigerant
charge.
Avoid the following
places for installation
where the air conditioner
malfunction
is
liable to occur.
Where there is too much oil in the air such as for machines
or cooking.
Salty environments
as seaside areas.
Hot-spring
areas.
Where sulfide gas exists.
Other special atmospheric
areas.
This unit has flared connections
on both indoor and outdoor sides. (Fig. 6-1)
Refrigerant
pipes are used to connect the indoor and outdoor units as shown in the
figure below.
• Insulate both refrigerant
and drainage piping completely
to prevent condensation.
Piping preparation
• Refrigerant pipes 3, 5, 7, 10 and 15 m [5 ft] are available as optional items.
(1) The specifications
of commercially
available
pipes.
Outside diameter
Min wall
Insulation
Model
Pipe
mm
inch
thickness
thickness
SEZ-
For liquid
6.35
1/4
0.8rnm [1/16 in] 8 mm[11/32 i n]
KD09
For gas
9.52
3/8
0.8rnm [1/16 in] 8 mm[11/32 i n]
SEZ-
For liquid
6.35
1/4
0.8rnm [1/16 in] 8 mm[11/32 i n]
KD 12
For gas
9.52
3/8
0.8rnm [1/16 in] 8 mm[11/32 i n]
SEZ-
For liquid
6.35
1/4
0.8rnm [1/16 in] 8 mm[11/32 i n]
KD15
For gas
12.7
1/2
0.8rnm [1/16 in] 8 mm[11/32 i n]
SEZ-
For liquid
6.35
1/4
0.8rnm [1/16 in] 8 mm[11/32 i n]
KD 18
For gas
12.7
5/8
1.0 rnm [1/16 in] 8 mm[11/32 i n]
Insulation
material
Heat-resistant
foam plastic,
0.045 specific
gravity
(2) Ensure that the two refrigerant
pipes are well insulated to prevent condensation.
(3) Refrigerant
pipe bending
radius must be 10 cm [3-15/16 in] or more.
/_, Caution:
Use insulation
of specified thickness.
Excessive
thickness
prevents storage
behind the indoor unit and smaller thickness
causes condensation.
6.2. Flaring work
• Main cause of gas leakage is defect in flaring work.
Carry out correct flaring work in the following procedure.
6.2.1.
Cutting
the pipes
[Fig. 6-3] (P.3)
Ca_ C opper tubes
(_) Good example
_ Bad examples
@ Tilted
_e_ Uneven
(_ Burred
• Use a pipe cutter cut the copper tube correctly.
6.2.2.
Burr
removal
[Fig. 6-4] (P.3)
Ca_ B urr
(_) Copper tube/pipe
_ Spare reamer
@ Pipe cutter
• Completely
remove all burrs from the cut section of pipe/tube.
• Point the end of the copper tube/pipe to downward
direction as you remove burrs in
order to avoid burrs drop in the tubing.
6.2.3.
Putting
nut on
[Fig. 6-5] (P.3)
Ca_ Flare nut
@ Copper tube
• Remove flare nuts attached to indoor and outdoor
unit, then attach them on pipe/
tube after burr removal.
(not possible to attach them on after flaring work)
6.2.4.
Flaring
work
[Fig. 6-6] (P.3)
Ca_ Flaring tool
(_ Die
_ Copper tube
@ Flare nut
Yoke
• Carry out flaring work using flaring tool as shown below.
Pipe diameter
(mm [in])
B -+°4[-u32](mm [in])
Dimension
A (ram [in])
When the tool for R410A is used
Clutch type
0 to 0.5 [0 to 1/32]
0 to 0.5 [0 to 1/32]
0 to 0.5 [0 to 1/32]
0 to 0.5 [0 to 1/32]
6.35 [1/4]
9.1 [3/8]
9.52 [3/8]
13.2 [17/32]
12.7 [1/2]
16.6 [21/32]
15.88 [5/8]
19.7 [25/32]
Firmly hold copper tube in a die in the dimension
shown in the table at above.
6.2.5.
Check
[Fig. 6-7] (P.3)
(_ Smooth
(_ Scratch on flared plane
@ Inside is shiny without any scratches
@ Cracked
@ Even length
@ Uneven
@ Toe much
(D Bad examples
@_ Tilted
• If flare is defective, cut off the flared section and repeat.
6.3. Pipe connection
[Fig. 6-8] (P.3)
• Apply a thin coat of refrigeration
oil on the surface of pipe.
• When connecting,
first align the center, then tighten the flare nut 3 to 4 turns.
• Use tightening torque table below as a guideline for indoor unit side union joint section,
and tighten using two wrenches. Excessive tightening damages the flare section.
Copper pipe O.D.
(mm [in])
66.35 [1/4]
69.52 [3/8]
612.7 [1/2]
615.88 [5/8]
Z_ Warning:
Flare nut O.D.
Tightening
torque
(mm [in])
(N.m)
17 [11/16]
14- 18
22 [7/8]
34- 42
26 [1-1/32]
49- 61
29 [1-5/32]
68- 82
Be careful
of removing
the flare nut! (Internally
pressurize
can cause them to
burst off.)
Remove the flare nut as follows:
1. Loosen the nut until you hear a hissing noise.
2. Do not remove the nut until the gas has been completely
released (i.e., hiss-
ing noise stops).
3. Check that the gas has been completely
released, and then remove the nut.
Outdoor
unit connection
Connect
pipes to stop valve pipe joint of the outdoor unit following the same proce-
dure as the indoor unit.
• For tightening,
use a torque wrench or spanner, and use the same tightening torque
procedure for indoor unit.
10

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents