Instance
Description
MI-2
Control Mode
MI-3
Operation Mode Status
Device Object Detail
Supported Properties
Object Identifier
Object Name
Object Type
Description
Model Name
System Status
Vendor Name
Vendor Identifier
Firmware Revision
Application Software
Version
Protocol Version
Protocol Revision
Protocol Service Supported
Protocol Object Types
Supported
Object List
Maximum APDU Length
Accepted
Segmentation Supported
BACnet T‐Stat User's Manual Rev 1.1, 7/28/11 
 
Writable?
Limits
Y
N
Writable?
N
N
QSTAT10000-0-1
N
N
Qstat10000
N
Qstat10000
N
N
Quest Controls
N
N
Major.Minor.Bug
N
Major.Minor.Bug
N
N
N
See BIBB list above
N
See Object list above
N
Object Count
N
N
Not supported
Default
1..4
1
1 – Auto (both cool and heat)
2 – Cooling only
3 – Heating only
4 - Off
1..6
0
1 – Off
2 – Cooling stage 1
3 – Cooling stage 2
4 – Heating stage 1
5 – Heating stage 2
6 – Heating stage 3
Default
Property Range
Restrictions
1
N/A
N/A
506
1
5
50
Notes
Notes
N/A
Note that the device
object id is the
MSTP Network *
1000 + the MAC
address.
N/A
Built up with model
name-MSTP
Network Address-
MAC Address
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Page | 11 