Analog Input Object Detail
Supported Properties
Object Identifier
Object Name
Description
Object Type
Present Value
Status Flags
Event State
Out of Service
Units
Instance
Description
AI-0
Raw Zone Temp
AI-1
Raw Supply Air
Analog Value Object Detail
Supported Properties
Object Identifier
Object Name
Description
Object Type
Present Value
Status Flags
Event State
Out of Service
Units
Instance
Description
AV-0
MAC Address
BACnet T‐Stat User's Manual Rev 1.1, 7/28/11 
 
Writable?
Writable?
N
Fahrenheit or Celsius reading of the zone thermistor, directly from
the sensor (no offsets applied).
A reading of -25F indicates an open sensor condition and a reading
of 150F indicates a shorted sensor condition.
N
Fahrenheit or Celsius reading of the supply air thermistor, directly
from the sensor (no offsets applied).
A reading of -25F indicates an open sensor condition and a reading
of 150F indicates a shorted sensor condition.
Writable?
Y (some)
Writable?
Units
Y
None
N
N
N
N
N
N
N
N
N
Notes
N
N
N
N
N
N
N
N
Limits
Default
1..127
1
MS/TP MAC address needs to be
unique in each network. You should
restart the unit after changing the
Property Range Restrictions
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Property Range Restrictions
N/A
N/A
N/A
N/A
Y
N/A
N/A
N/A
N/A
Notes
Page | 3 