Quest Controls BACnet T­Stat User Manual page 22

Table of Contents

Advertisement

 
Instance
Description
AV-51
Sun Sched Win 2 Start
AV-52
Sun Sched Win 2 End
AV-53
Curr User Spt Adjust
AV-54
Front Panel Code
Binary Input Object Detail
Supported Properties
Object Identifier
Object Name
Description
Object Type
Present Value
Status Flags
Event State
Out of Service
Polarity
Instance
Description
BI-0
Fan Proof
Binary Value Object Detail
Supported Properties
Object Identifier
Object Name
Description
Object Type
BACnet T‐Stat User's Manual Rev 1.1, 7/28/11 
 
Writable?
Units
Y
Minutes
Y
Minutes
Y
TempF or
TempC
Y
None
Writable?
Writable?
N
The current reading of the fan proof input.
Writable?
Limits
Default
window.
Set both the Start and End values to
0 to mark this window as unused.
0..1440
0
Number of minutes since midnight
to begin occupied mode for this
window.
0..1440
0
Number of minutes since midnight
to end occupied mode for this
window.
Set both the Start and End values to
0 to mark this window as unused.
0..AV16
N/A
The current setpoint offset a user has
entered via the front panel.
0,11..99
0
The access code a user must enter to
use the front panel programming
menu.
N
N
N
N
N
N
N
N
N
Notes
N
N
N
N
Notes
Property Range Restrictions
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Property Range Restrictions
N/A
N/A
N/A
N/A