Supported Properties
Present Value
Status Flags
Event State
Out of Service
Polarity
Instance
Description
BV-0
Temperature Units
BV-1
Occupied Fan Mode
BV-2
Unoccupied Fan Mode
BV-3
Force Occupied Mode
BV-4
Zone Sensor Location
Binary Output Object Detail
Supported Properties
Object Identifier
Object Name
Description
Object Type
Present Value
Status Flags
Event State
Out of Service
Polarity
Priority Array
* - The binary output object utilizes the priority array 1 through 16. A BACnet client can see the system's output
desire at priority 16 and is free to write any of the other 15 priorities.
Instance
Description
BO-0
Output G
BACnet T‐Stat User's Manual Rev 1.1, 7/28/11 
 
Writable?
Y (Priority array not available)
Writable?
Y
Y
Y
Y
Y
Writable?
Writable?
Y
0 – De-energize Output
1 – Energize Output
Property Range Restrictions
N
N
N
N
Default
0
0 – Use Fahrenheit
1 – Use Celsius
0
0 – Fan mode auto
1 – Fan mode always on
0
0 – Fan mode auto
1 – Fan mode always on
N/A
0 – Remove BACnet occupied
override
1 – Enable BACnet occupied
override
0
0 – Use onboard zone thermistor
1 – Use remote mounted zone
thermistor
Property Range Restrictions
N
N
N
N
Y*
N
N
N
N
Y*
Notes
N/A
N/A
N/A
N/A
N/A
Notes
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Page | 9 