SAJ Sununo-TL Series User Manual page 8

Sununo-tl series solar inventer
Hide thumbs Also See for Sununo-TL Series:
Table of Contents

Advertisement

Type
Sununo-TL3KB
Input (DC)
Max. DC Power [W]
Max. DC Voltage [V]
MPPT Voltage Range [V]
MPPT Voltage Range[V](Full Load)
DC Nominal Voltage [V]
Start Voltage [V]
Min. DC Voltage [V]
Max. DC Current Input [A]
Number of DC Connection Sets
Number of MPP Trackers
DC Switch
Output (AC)
Rated AC Power [W]
Max. AC Power [W]
Rated AC Current [A]
Max. AC Current [A]
Norminal AC Voltage/Range
Grid Frequency/Range
Power Factor(cos φ)
AC Current Distortion (THD)
Consumption at Night [W]
Consumption at Standby [W]
Efficiency
Max. Efficiency
Euro Efficiency (at 360Vdc)
MPPT Accuracy
Protection
Internal Overvoltage Protection
DC Insulation Monitoring
DC Side Varistors
Direct Current Monitoring
Ground Fault Current Monitoring
Grid Monitoring
AC Short Current Protection
Thermal Protection
Anti-island protection monitoring
Interface
AC Connection
DC Connection
LCD Display
LCD(16x2 Characters
Display Language
Datalogger & Communication
2*RS485(Standard)
General Data
Isolation
Operating Temperature Range
Cooling Method
Ambient Humidity
Site Altitude above Sea Level
Noise Emission dBA)
(
IP Protection
Mounting
Dimensions (WxHxD) [mm]
Weight [kg]
Standard Warranty (Year)
Safety Class Compliance
EMC Compliance
EN61000-6-2,EN61000-6-3,EN61000-3-2,EN61000-3-3
VDE 0126-1-1/A1,VDE 4105, G83,RD1699, C10/11,
Grid Protection Compliance
Remarks: Meet the grid standard AC current per phase not exceeding 16A.
User Manual
Sununo-TL4KB
3400
4500
550
125-440
200-440
225-440
360
150
100
17
20
2
1
Optional
3000
4000
3300
4400
1
13.0
17.4/16
15.0
1
20.0/16
220V, 230V, 240V/180V-280V
50Hz, 60Hz/ ±5Hz
>0.99[full load]
< 2%
<0.2
6
97.7%
97.7%
97.1%
97.1%
>99.5%
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
AFD
Terminals
MC4/H4
Backlight) & LED(3 Lights)
Multi Language
Wi-Fi/Ethernet(Optional)
Transformerless
-25°C to +60°C [45°C to 60°C with derating ]
Natural Convection
0% to 98% Non-condensing
Up to 2000m
<40
IP65 [Indoor or Outdoor Installation]
Rear Panel
450*375*177
21
5 / 10/15/20/25 [Optional]
AS3100, IEC62109-1,IEC62109-2
AS4777.3,EN50438,CGC/CF004
9
Type
Sununo-TL3KA
Input (DC)
Max. DC Power [W]
Max. DC Voltage [V]
MPPT Voltage Range [V]
MPPT Voltage Range[V](Full Load)
DC Nominal Voltage [V]
Start Voltage [V]
Min. DC Voltage [V]
Max. DC Current Input A/Input B[A]
Number of DC Connection Sets
Number of MPP Trackers
DC Switch
Output (AC)
Rated AC Power [W]
Max. AC Power [W]
Rated AC Current [A]
Max. AC Current [A]
Norminal AC Voltage/Range
Grid Frequency/Range
Power Factor(cos φ)
AC Current Distortion (THD)
Consumption at Night [W]
Consumption at Standby [W]
Efficiency
Max. Efficiency
Euro Efficiency (at 360Vdc)
MPPT Accuracy
Protection
Internal Overvoltage Protection
DC Insulation Monitoring
DC Side Varistors
Direct Current Monitoring
Ground Fault Current Monitoring
Grid Monitoring
AC Short Current Protection
Thermal Protection
Anti-island protection monitoring
Interface
AC Connection
DC Connection
LCD Display
LCD(16x2 Characters Backlight) & LED(3 Lights)
Display Language
Datalogger & Communication
2*RS485(Standard)
General Data
Isolation
Operating Temperature Range
Cooling Method
Ambient Humidity
Site Altitude above Sea Level
Noise Emission dBA)
(
IP Protection
Mounting
Dimensions (WxHxD) [mm]
Weight [kg]
Standard Warranty (Year)
Safety Class Compliance
EMC Compliance
EN61000-6-2,EN61000-6-3,EN61000-3-2,EN61000-3-3
VDE 0126-1-1/A1,VDE 4105, G83,G59,RD1699, C10/11,
Grid Protection Compliance
Remarks: Meet the grid standard AC current per phase not exceeding 16A.
User Manual
Sununo-TL4KA
3200
4200
550
125-440
200-440
360
150
100
15/15
15/15
2
2
Optional
3000
4000
3000
4000
1
13.0
17.4/16
15.0
1
20.0/16
220V, 230V, 240V/180V-280V
50Hz, 60Hz/ ±5Hz
>0.99 [full load]
< 2%
<0.2
6
97.6%
97.6%
96.8%
96.8%
>99.5%
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
AFD
Terminals
MC4/H4
Multi Language
Wi-Fi/Ethernet(Optional)
Transformerless
-25°C to +60°C [45°C to 60°C with derating ]
Natural Convection
0% to 98% Non-condensing
Up to 2000m
<40
IP65 [Indoor or Outdoor Installation]
Rear Panel
525*425*175
23
5 / 10/15/20/25 [Optional]
AS3100, IEC62109-1,IEC62109-2
AS4777.3,EN50438,CGC/CF004
10

Hide quick links:

Advertisement

Table of Contents
loading