Power Supply Cord; Fire Hazard - Kenmore 27 IN. (69 CM) Installation Instructions Manual

27 in. (69 cm) electric dryer
Hide thumbs Also See for 27 IN. (69 CM):

Advertisement

Available languages

Available languages

Power S upply Cord
Direct W ire
FireHazard
Usea
new UL approved 30 amp power supply cord.
Use a UL approved strain relief.
Disconnect power before making electrical connections.
Connect neutral wire (white or center wire) to center
terminal (silver).
Ground wire (green or bare wire) must be connected to
green ground connector.
Connect remaining 2 supply wires to remaining
2 terminals (gold).
Securely tighten all electrical connections.
Failure to do so can result in death, fire, or
electrical shock.
Fire Hazard
Use 10 gauge solid copper wire.
Use a UL approved strain relief.
Disconnect power before making electrical connections.
Connect neutral wire (white or center wire) to center
terminal (silver).
Ground wire (green or bare wire) must be connected to
green ground connector.
Connect remaining 2 supply wires to remaining
2 terminals (gold).
Securely tighten all electrical connections.
Failure to do so can result in death, fire, or
electrical shock.
1. Disconnect power.
2.
Remove the hold-down
screw and terminal block cover.
1
2
3
4
5
6
1. Terminal block cover
2. External ground connector
3, Center, silver-colored
terminal block screw
4. Hold-down
screw
5. Neutral grounding
wire (green/yellow)
6. Hole below terminal block opening
31
41
Assemble a s/4in. (1,9 cm) UL approved strain relief (UL
marking on strain relief) into the hole below the terminal block
opening. Tighten strain relief screws just enough to hold the
two clamp sections together. Put power supply cord through
the strain relief, The strain relief should have a tight fit with the
dryer cabinet and be in a horizontal position.
Now complete installation following instructions
for your type
of electrical connection:
4-wire (recommended)
3-wire (if 4-wire is not available)
4