Haier 10571570 Operation Manual page 27

Two by one room air conditioner
Table of Contents

Advertisement

Installation procedure
Original cement panel
Use the in hole hinge, in hole plug or in hole screw.
Directly use angle steel or new angle steel for support.
Suspending of indoor unit
Adjust the position of screw cap
(underside) to make the gap between
the attached washer (underside) and
the ceiling is 135mm.
*. Installation of indoor unit
Tighten the screw cap of the hoisting screw and suspend them on the T
groove of the unit suspending part.
Use gradienter to keep the level degree of the unit within 5mm.
Use installation paper panel to confirm and adjust the position relation
between unit and ceiling opening and the suspending height of the unit.
(shows the using direction of the installation paper panel)
*The bottom of indoor unit is 43mm away from the bottom of ceiling.
(4 corners)
*The side of the indoor unit leaves 25mm gaps from ceiling.
Gradienter
Indoor unit
Ceiling
4 edges together
Suspending bolt (M8 or M10)
Screw cap (M8 or M10)
Hoisting screw
Suspending pole
Installation paper panel
Install indoor unit
Suspending bolt
Hoisting screw
Hoisting screw
Screw cap (upside)
M10 screw
Ceiling
The fittings should be prepared on site except for M10 flat washer
M10 or M8 flat washer
M10 or M8 flat washer
In order to prevent the bolt from breaking off
(safety), they must be installed blow the sus
pending parts as this figure shown.
Screw cap (M8 or M10)
43mm
25mm
Angle steel for support
Attached washer
(The suspending part of the unit)
Screw cap (underside)