Installation procedure
5 . Refrigerant pipe
[The proper thermal insulation must be treated to gas pipe and liquid pipe. If not,
it may cause water leakage.]
The outdoor unit is not charged with refrigerant.
When connecting the pipes to unit or dismantling the pipes from the unit, do
proceed as the figure shown, use spanner and torque pincers together.
For the dimension of the cone-shaped screw nut, please referring to Table 1.
When connecting pipes, both the inner or the outside of the cone-shaped screw
nut should pasted with refrigerant oil. Use hands to twist it for 3~4 circles, then
tighten it.
According to Table 1 to confirm the fasten torque. (fasten too tight may damage
the screw nut leading to leakage)
After check if the connection pipes leaks, then perform thermal insulation
treatment, as the following figure shown.
Only use seal cushion to bind the joint between gas pipe and the insulation parts.
Paste refrigerant oil here
Table 1
Specification of pipe (mm)
9.52
15.88

6 . Installation of drain hose

(1)Install the drain hose
The diameter of the drain hose should be larger than or equal to the
diameter of connection pipe.
(Polyethylene pipe, dimension: 25mm, external diameter:32mm)
Material of connection pipe
Material of thermal insulation
26
Torque spanner
Spanner
Pipe joint
Cone-shaped screw nut
Torque
3270*3990 N . cm
(333*407 kgf . cm)
6180*7450 N . cm
(630*770 kgf . cm)
Medium seal cushion (accessory)
(use seal cushion to bind the pipe joint)
Clamp
Liquid pipe
Dimension of cone A (mm)
12.0 *12.4
18.6*19.0
Stiff PVC pipe VP 31.5mm (inside diameter)
Foam polyethylene pipe, thickness over 10mm
Install indoor unit
Thermal insulation part (accessory)
(for liquid pipe)
Thermal insulation part (accessory)
(for gas pipe)
Gas pipe
Cone
45
2
90
0.5
A
R0.4~0.8