Generac Power Systems Guardian 04389-2 Installation And Owner's Manual

Air-cooled, prepackaged automatic standby generators
Hide thumbs Also See for Guardian 04389-2:
Table of Contents

Advertisement

Not intended for use as Primary Power in place of utility or in
!
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!!
Installation and
Owner's Manual
life-support applications.
DANGER
Air-cooled, Prepackaged
Automatic Standby Generators
Models:
04389-2 (6 kW NG, 7 kW LP)
04456-2 (12 kW NG, 12 kW LP)
04390-2 (13 kW NG, 15 kW LP)
GENERAC
R
POWER SYSTEMS, INC.
R
!

Advertisement

Table of Contents
loading

Summary of Contents for Generac Power Systems Guardian 04389-2

  • Page 1 DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!! Installation and Owner’s Manual Automatic Standby Generators GENERAC POWER SYSTEMS, INC. life-support applications. DANGER Air-cooled, Prepackaged Models: 04389-2 (6 kW NG, 7 kW LP) 04456-2 (12 kW NG, 12 kW LP) 04390-2 (13 kW NG, 15 kW LP)
  • Page 2: Introduction

    Guardian models: • 04389-2 – 6 kW NG, 7 kW LP , single-cylinder GH- 410 Engine • 04456-2 – 12 kW NG, 12 kW LP , V-twin GT-990 Engine •...
  • Page 3: Table Of Contents

    Introduction ...Inside Front Cover Read This Manual Thoroughly ...IFC Contents ...IFC Operation and Maintenance ...IFC How to Obtain Service ...IFC Authorized Dealer Locator Number ...IFC Safety Rules ...2 Standards Index ...3 Section 1 – General Information ...4 Unpacking/Inspection ...4 Protection Systems ...4 NEC Requirement for Arc Fault Circuit Interruption Breaker for Bedrooms ...4 The Generator ...5...
  • Page 4: Safety Rules

    IMPORTANT SAFETY INSTRUCTIONS Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
  • Page 5: Standards Index

    ELECTRICAL HAZARDS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion.
  • Page 6: Section 1 - General Information

    Section 1 — General Information Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators DANGER Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations. UNPACKING/INSPECTION After unpacking, carefully inspect the contents for damage.
  • Page 7: The Generator

    THE GENERATOR Figure 1.1 – 7 kW, Single Cylinder GH-410 Engine Exhaust Enclosure Figure 1.2 – 12 kW and 15 kW, V-twin GT-990 Engine Exhaust Enclosure Section 1 — General Information Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Oil Check/Fill Data Decal Battery Compartment...
  • Page 8: Specifications

    Compression Ratio Starter Oil Capacity Including Filter Recommended Oil Filter Recommended Air Filter Operating RPM Generac ® Power Systems, Inc. Model 04389-2 Model 04456-2 6,000 NG/7,000 LP 12,000 NG/12,000 LP 120/240 120/240 50.0 NG/58.3 LP 100.0 NG/100.0 LP 25.0 NG/29.2 LP 50.0 NG/50.0 LP...
  • Page 9: System Set Led

    SYSTEM SET LED The “System Set” LED is lit when all of the following conditions are true: 1. The AUTO/OFF/MANUAL switch is set to the AUTO position. 2. The utility voltage being supplied to the unit is being sensed by the PCB. If the utility sense volt- age is not connected to the unit or if it is below 168 volts AC, then the system set light will flash rapidly.
  • Page 10: Location

    Section 1 — General Information Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators NOTE: The natural gas adjustment screw is preset during installation and should not need any further adjustment. 1.9.2 12KW AND 15KW, 990CC ENGINES To reconfigure the fuel system from NG to LP , follow these steps: NOTE: The primary regulator for the propane supply is...
  • Page 11: Battery Installation

    • Install the transfer switch indoors on a firm, stur- dy supporting structure. • To prevent switch distortion, level the switch if nec- essary. This can be done by placing washers between the switch enclosure and mounting sur- face. • Never install the switch where water or any corro- sive substance might drip onto the enclosure.
  • Page 12: Section 2 - Post Installation Start-Up And Adjustments

    Section 2 — Post Installation Start-up and Adjustments Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic. The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes.
  • Page 13: Generator Tests Under Load

    7. When certain that utility supply voltage is com- patible with transfer switch and load circuit rat- ings, turn OFF the utility power supply to the transfer switch. 8. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL. The engine should crank and start.
  • Page 14: Adjusting The Regulator (Natural Gas Only)

    Section 2 — Post Installation Start-up and Adjustments Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 5. Turn ON the utility power supply to the transfer switch, using the means provided (such as a util- ity main line circuit breaker). 6.
  • Page 15: Engine Governor Adjustment

    If this procedure or the equipment are not available, locate the nearest Generac Guardian Dealer and they can perform the adjustments. NOTE: A service fee may be charged for this adjustment. ENGINE GOVERNOR ADJUSTMENT If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows: 2.7.1 7 KW UNITS...
  • Page 16: Section 3 - Operation

    Section 3 — Operation Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators NOTE: The access panel on top of the control panel must be removed to adjust the voltage regulator. NOTE: The voltage regulator is housed above the genera- tor's control panel.
  • Page 17: Sequence Of Automatic Operation

    3. Set the generator’s AUTO/OFF/MANUAL switch to AUTO. 4. Set the generator’s main circuit breaker to its ON (or closed) position. With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source.
  • Page 18: Setting The Exercise Timer

    Section 3 — Operation Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 3.5.2 TRANSFER BACK TO UTILITY POWER SOURCE When utility power has been restored, transfer back to that source and shut down the generator. This can be accomplished as follows: 1.
  • Page 19: Section 4 - Maintenance

    NOTE: If the fault is not repaired, the overcrank feature will continue to activate. 3.7.3.1 Approximate Crank Cycle Times • 15 seconds ON • 7 seconds OFF • 7 seconds ON • 7 seconds OFF • Repeat for 45 seconds Approximately 90 seconds total 3.7.4 OVERSPEED...
  • Page 20: Changing The Engine Oil

    Section 4 — Maintenance Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators CHANGING THE ENGINE OIL 4.3.1 ENGINE OIL RECOMMENDATIONS Use oil of American Petroleum Institute (API) Service Class SG, SH or SJ. Use all season SAE 5W-30 Synthetic oil.
  • Page 21: Spark Plug(S)

    Figure 4.7 — 12 kW and 15 kW Engine Air Cleaner Screw SPARK PLUG(S) Reset the spark plug(s) gap or replace the spark plug(s) as necessary. See Section 4.13 for mainte- nance requirements. 1. Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine.
  • Page 22: Adjusting Gh-410/Gt-990 Valve Clearance

    Section 4 — Maintenance Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed: • DO NOT SMOKE when near the battery; •...
  • Page 23: Attention After Submersion

    The exhaust from this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system. The maximum ambient temperature for the generator is 40°...
  • Page 24: Service Schedule

    Section 4 — Maintenance Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 4.13 SERVICE SCHEDULE ATTENTION: It is recommended that all service work be performed by the nearest Generac/Guardian Authorized Dealer. SYSTEM/COMPONENT X = Action R = Replace as Necessary * = Notify Dealer if Repair is Needed.
  • Page 25: Section 5 - Troubleshooting

    TROUBLESHOOTING GUIDE PROBLEM The engine will not crank. The engine cranks but will not start. The engine starts hard and runs rough. The Auto/Off/Manual switch is set to OFF , but the engine continues to run. There is no AC output from the generator.
  • Page 26: Section 6 - Electrical Data

    Section 6 — Electrical Data Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 12 & 15 kW – Drawing No. 0D8500-B DIAGRAM KEY BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - MAIN OUTPUT BREAKER CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATION D - DIODE DSW - PCB MOUNTED DIP SWITCH...
  • Page 27 224A 225A 225B 225B 224B 224B VOLTAGE REGULATOR Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 12 & 15 kW – Drawing No. 0D8500-B CONTROL PANEL BOX 224A 225A AUTO MANUAL Section 6 — Electrical Data CLOSEST TO BEARING 240V GENERATOR OUTPUT TO TRANSFER...
  • Page 28 Section 6 — Electrical Data Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – 12 & 15 kW – Drawing No. 0D8501-B C2-11 FIELD ELECTRONIC C2-10 VOLTAGE REGULATOR C2-8 (STATOR) DIAGRAM KEY BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - CIRCUIT BREAKER, MAIN OUTPUT CB2 - CIRCUIT BREAKER, ALT.
  • Page 29 225A 56VA 224A C1-1 C1-5 Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – 12 & 15 kW – Drawing No. 0D8501-B C2-6 C2-5 POWER WINDING (STATOR) C2-1 Section 6 — Electrical Data 240VAC UTILITY INPUT 12Vdc TRANSFER RELAY...
  • Page 30 Section 6 — Electrical Data Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 7 kW – Drawing No. 0D9013-C DIAGRAM KEY BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - MAIN OUTPUT BREAKER CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATION D - DIODE DSW - PCB MOUNTED DIP SWITCH...
  • Page 31 224A 225A 224A 225B 225B 224B 224B VOLTAGE REGULATOR Section 6 — Electrical Data Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 7 kW – Drawing No. 0D9013-C CONTROL PANEL BOX 225A AUTO MANUAL CLOSEST TO BEARIN STATOR 240V GENERATOR OUTPUT TO TRANSFER...
  • Page 32 Section 6 — Electrical Data Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – 7 kW – Drawing No. 0D9014-C ELECTRONIC C2-10 VOLTAGE REGULATOR C2-8 DPE WINDING (STATOR) DIAGRAM KEY BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - CIRCUIT BREAKER, MAIN OUTPUT CB2 - CIRCUIT BREAKER, ALT.
  • Page 33 C2-6 225A 56VA 224A C1-1 C1-5 Section 6 — Electrical Data Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – 7 kW – Drawing No. 0D9014-C C2-5 POWER WINDING (STATOR) C1-2 C1-6 240VAC UTILITY INPUT 12Vdc TRANSFER RELAY COIL...
  • Page 34: Section 7 - Exploded Views And Parts Lists

    Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Enclosure – Drawing No. 0D3416-R PRE PACKAGED UNITS ONLY 44 85 79 80 32 Generac ® Power Systems, Inc. 49 49...
  • Page 35 ITEM PART NO. QTY. DESCRIPTION 0C6140 ASSEMBLY, ENCLOSURE BASE 0D1901 ASSEMBLY, ENCLOSURE BASE (7KW) 0C6735 SUPPORT, ROOF FOLDING 0C7061 ENCLOSURE, FRONT 0C7062 ENCLOSURE, EXHAUST SIDE 0C7062A ENCLOSURE, EXHAUST SIDE (7KW) 0C7063 ENCLOSURE, SIDE & BACK 0C7063A ENCLOSURE, SIDE & BACK (7KW) 0C7064 ENCLOSURE, ROOF 0C7065...
  • Page 36 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Control Panel – Drawing No. 0E7974 34 Generac ® Power Systems, Inc.
  • Page 37 ITEM PART NO. QTY. DESCRIPTION 0E7886A CIRCUIT BREAKER 30A X 2P 240V (7KW) 0E7886C CIRCUIT BREAKER 40A X 2P 240V (8.5KW) 0E7886E CIRCUIT BREAKER 50A X 2P 240V (12KW) 0E7886F CIRCUIT BREAKER 60A X 2P 240V (13KW) 0E7886G CIRCUIT BREAKER 70A X 2P 240V (15KW) 0A1801 ASSEMBLY, BATTERY CHARGER ENGINE...
  • Page 38 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 7 kW GTS Load Center Assembly – Drawing No. 0E7975 36 Generac ® Power Systems, Inc.
  • Page 39 ITEM PART NO. 0D4801 0D4800 0C2237 077220 077220A 082574 084464 074908 024912 0A1658 063617 0E7889A 0A1495 0A1661 022473 0D3094 0D4684A 0E7900 056326 022152 087680 077441 063378 0A2110 074138 036933 077033 048850 028739 0D4802 0D3191 0D3088 073591 073590A 040213B 0E7888C 0A7215 0E7888B 0E7888A 0D3320...
  • Page 40 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 12 kW and 15 kW GTS Load Center Assembly – Drawing No. 0E7973-A 38 Generac ® Power Systems, Inc.
  • Page 41 12 kW and 15 kW GTS Load Center Assembly – Drawing No. 0E7973-A ITEM PART NO. 0D3086 0D3092 0C2237 077220 077220A 082574 084464 074908 024912 0A1658 063617 0E7889 0A1495 0A1661 022473 055450 0D4684 0E7900 056326 022152 087680 077441 063378 0D3094 074138 036933 077033...
  • Page 42 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990 Engine – Drawing No. 0D8674-G Part 1 40 Generac ® Power Systems, Inc.
  • Page 43 ITEM PART NO. QTY. DESCRIPTION 0C5729 ASSEMBLY, CRANKCASE HOUSING WITH SLEEVE 0C3008 SEAL, 38 I.D. CRANKSHAFT 090388 SCREW, TAPTITE M6-1.0 X 12 YC 0C5372 ASSEMBLY, BREATHER 0C3005 GASKET, BREATHER COVER 0E3372B SEPARATOR, OIL BREATHER 0D8067A ASSEMBLY, HEAD #1 G&S 071983 RETAINER, PISTON PIN 20 0C2981C ROCKER, COVER NO OIL FILL...
  • Page 44 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990/760 Engine – Drawing No. 0D8674-G Part 2 42 Generac ® Power Systems, Inc. 11 116...
  • Page 45 ITEM PART NO. QTY. DESCRIPTION 0C5136A KNOB, AIR CLEANER 0C3024 COVER, AIRBOX NG/LP 0C3040 PRE-CLEANER, 0C8127 ELEMENT, AIR CLEANER 0D8564A ASSEMBLY, MIXER/AIRBOX 990 0D8564B ASSEMBLY, MIXER/AIRBOX 760 0D2595 SCREW SHOULDER (8MM) M6-1.0 X 18 0D4417 WASHER,RUBBER 1/4" X 1/8" THICK 0C3025 SWITCH, OIL PRESS 0D3083...
  • Page 46 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 7 kW Generator – Drawing No. 0D3504-C 44 Generac ® Power Systems, Inc.
  • Page 47 ITEM PART NO. 0C6934 0C9935H 0C9934H 0C6043A 0C8096 0C9593 0D3220 0C8860 031971 0C3168 056147 0D1847 0C7038C 0D1647 0D2558 0C7038B 0C7758 0388050AE0 0C2417A 082121C 066386 029451 049451 022237 022511 022131 039287 022145 049820 090388 022129 022259 059637 048031K 0C9592 057822 040976 0C2824 025145 090239...
  • Page 48 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 12 kW and 15 kW Generator – Drawing No. 0D3417-E 46 Generac ® Power Systems, Inc.
  • Page 49 ITEM PART NO. 0C6934 0C7930 0D2359 0C7944 0D2356 0C6043 0D2336 0D6634 0D3220 0C8101 056482 0C3168 0D1838 0D1846 0C7038 0D1609 0D2559 0C7038A 0C7758 0388050AD0 0C2417A 082121C 066386 029451 049451 022237 022511 022131 039288 022145 049820 045756 022129 022259 059637 083512 074994 057822 052858 0C2824...
  • Page 50 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GN410 Engine – Drawing No. 0D3539-F Part 1 48 Generac ® Power Systems, Inc.
  • Page 51 ITEM PART NO. 071978 071980 021533 0C5848 071983 0D4287 0A7628 078658 078659 088261E 0E3812 0A7975 078645 0A7811 0A9877 076701 021713B 078691 0A5771 0A5776 076361 0A8898D 0D2274 0C4391 086025 0C7393 021714 086516 086517 0D9853B 083897 077158 0C3150 072694 083907 072696 078694 021742 0D6094 076329...
  • Page 52 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GN410 Engine – Drawing No. 0D3539-F Part 2 50 Generac ® Power Systems, Inc.
  • Page 53 ITEM PART NO. 0C1069 0D2922 0C8435 0C9997 088434 045756 088433B 0D9004A 059985 022129 0C2458A 083512 0D1401A 091039 0C9619 049811 022097 040945 086999 0D5667A 049821 099236 070185 082774 091222E 067198N 067890 072347 072734 072735 0C3978 0C6040 0D9760 092079 0A8222 083502 082025 0D3083 0C8434 090072...
  • Page 54 Section 7 — Exploded Views and Parts Lists Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Gas Regulator – Drawing No. 0D8720-B ITEM PART NO. QTY. DESCRIPTION 0D5694 CASTING, TWIN REGULATOR HOUSING 0C5765 SOLENOID, TWIN REGULATOR 0C4647 GASKET , SOLENOID 0C4680 PLUNGER, LP REGULATOR ASSEMBLY 0C6070...
  • Page 55: Section 8 - Mounting Dimensions

    Section 8 — Mounting Dimensions Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Drawing No. 0D3739-B Generac ® Power Systems, Inc. 53...
  • Page 56: Section 9 - Notes

    Section 9 — Notes Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 54 Generac ® Power Systems, Inc.
  • Page 57 Section 9 — Notes Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Generac ® Power Systems, Inc. 55...
  • Page 58: Section 10 - Warranty

    Section 10 – Warranty Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below. CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT YOUR WARRANTY RIGHTS AND OBLIGATIONS The California Air Resources Board (CARB) and Generac Power Systems, Inc.
  • Page 59: Emission Control System Warranty

    Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con- tinue for 24 consecutive months thereafter.
  • Page 60 Section 10 – Warranty Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GENERAC POWER SYSTEMS STANDARD "TWO YEAR" LIMITED WARRANTY FOR GUARDIAN “EMERGENCY AUTOMATIC STANDBY GENERATORS” For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below.