Chemical Vapor Corrosion - State Water Heaters GS6 40 YBVIS Installation And Operating Manual

Power vented gas models with hot surface ignition
Table of Contents

Advertisement

Figure 18.
4. When ducts are used, they shall be of the same
cross-sectional area as the free area of the openings
to which they connect. The minimum short side
dimension of rectangular air ducts shall not be less
than 3" (see Figure 19).
Figure 19.
5. Alternatively a single permanent opening may
be used when communicating directly with the
outdoors, or with spaces that freely communicate
with the outdoors. The opening shall have a
minimum free area of 1 square inch per 3,000 Btu/
hr of total input rating of all equipment in enclosure
(see Figure 20).
6. Louvers and Grilles: In calculating free area,
consideration shall be given to the blocking effect
of louvers, grilles or screens protecting openings.
Screens used shall not be smaller than 1/4" mesh.
If the free area through a design of louver or grille
is known, it should be used in calculating the size
opening required to provide the free area specifi ed.
If the design and free area is not known, it may be
assumed that wood louvers will be 20-25 percent
free area and metal louvers and grilles will have
60-75 percent free area. Louvers and grilles shall
be fi xed in the open position or interlocked with the
equipment so that they are opened automatically
during equipment operation.
7. Special Conditions Created by Mechanical
Exhausting or Fireplaces: operation of exhaust fans,
ventilation systems, clothes dryers or fi replaces may
create conditions requiring special attention to avoid
unsatisfactory operation of installed gas utilization
equipment.

CHEMICAL VAPOR CORROSION

CORROSION OF THE FLUEWAYS AND VENT SYSTEM
MAY OCCUR IF AIR FOR COMBUSTION CONTAINS
CERTAIN CHEMICAL VAPORS. SUCH CORROSION
MAY RESULT IN FAILURE AND RISK OF ASPHYXIATION.
Spray can propellants, cleaning solvents, refrigerator and
air conditioning refrigerants, swimming pool chemicals,
calcium and sodium chloride (water softener salt), waxes,
and process chemicals are typical compounds which
are potentially corrosive. Do not store products of this
sort near the heater. Also air which is brought in contact
with the heater should not contain any of the chemicals.
If necessary, uncontaminated air should be obtained
from remote or outside sources. The Limited Warranty is
voided when failure of water heater is due to a corrosive
atmosphere. See "Limited Warranty" for complete terms
and conditions.
www.statewaterheaters.com
Figure 20.
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gs6 50 yrvhslGs6 75 yrvhtlGs 6

Table of Contents