If the openings will bring air directly from the
outdoors, two openings are required, and they
should be sized to give a minimum free area of
one square inch for every 4000 BTUH of the
maximum input rating of the unit.
If the openings will bring air from another indoor
area, they should be sized to give a minimum free
area of one square inch for every 1000 BTUH of
the maximum input rating of the unit.
One of these openings should be within 12" of the
ceiling, and the other should be within 12" of the
floor.

Exhaust Venting

This water heater must be vented in accordance
with the section on venting of equipment in the
latest edition of the National Fuel Gas Code.
This is a Category III appliance, and must be
vented accordingly. The following are UL listed
manufacturers: Z-Flex Inc. ProTech Systems
FasNSeal, Z Vent II and Heat-Fab Inc. Saf-T Vent.
Follow the vent pipe manufacturer's instruction
when installing the vent pipe.
vent this appliance with any other vented
appliance.
The venting system must not exceed a length of
21 ft. minus 5 ft. for every elbow. Do not use more
than 3 elbows.
No. of Elbows
0
1
2
3
If the horizontal vent run exceeds 5 ft., the
following criteria must be observed:
There must be a 2 ft. vertical run off the top
of the heater before the horizontal run
begins.
The horizontal run must be supported at 3'
intervals.
The vent run should be pitched up towards
the termination at ¼" per foot.
The unit can be vented either up and out the roof,
or directly through a wall. If the unit will be vented
through a wall, use Takagi USA Inc. optional part,
the TK-TV01 vent terminator, or an equal Category
III vent part. Locate the vent terminator according
to ANSI Z223.1/NFPA 54 and applicable local
codes.
Maintain
the
following
combustible surface in an indoor installation:
Do not common
Max. Vertical or
Horizontal Length
21 ft.
16 ft.
11 ft.
6 ft.
clearances
to
Piping side
Front (Maintenance
space)
Back of heater
Non piping side
Top of heater

Manufactured Home (Mobile Home) Installation

This appliance must be installed in accordance
with the Manufactured Home Construction and
Safety Standard, (Title 24, CFR; Part 3280) and
ANSI A119.5/NFPA 501D. In addition, install in
accordance with the following instructions, the
instructions supplied with any venting, local codes,
utility company requirements for the installation of
water heaters in manufactured homes (mobile
homes), and the latest edition of the National Fuel
Gas Code, ANSI Z221.3/NFPA 50.
Locate the heater in an enclosure separating the
unit
from
manufactured home or trailer. All combustion air
must be obtained from the outside atmosphere,
and the flue gases must be discharged directly
outdoors through a gas vent. There must be no
opening from the interior of the home or trailer into
the water heater enclosure.
Indoor Installation
Follow indoor installation instructions as set out in
an earlier section of this manual, except that
combustion air must not be taken from the inside
of the home or trailer.
Outdoor Installation
Follow outdoor installation instructions as set out in
an earlier section of this manual.
If the unit is to be installed in a recessed area,
connect a gas vent to the unit, which will direct
exhaust gases out of the recessed area.
any
11
Indoor Clearances
Suggested 24"
Floor
Noncombustible base
the
internal
atmosphere
Indoors
Outdoors
Min. 32"
Min. 3"
6"
Min. 4"
1"
2"
11"
of
the
Min. 3"