Gas Supply Piping - RBI SERIES 8800 Installation & Operation Manual

Gas boilers (model hb) & water heaters (model hw)
Table of Contents

Advertisement

Page 20
SERIES 8800 & 8900 INSTALLATION AND OPERATING INSTRUCTIONS

GAS SUPPLY PIPING

WARNING: Check the boiler/water heater rating
plate to make sure that the boiler/water heater
is for the type of gas that will be used. If it isn't,
do not connect the boiler/water heater to the gas
supply. Gas supply piping must be in accordance
with the National Fuel Code, ANSI Z223.1-latest
revision or applicable provisions of the local
building codes. Canadian installations must
comply with CAN/CGA B149.1 or .2 Installation
Code. Failure to comply with this warning can
result in extensive property damage, severe
personal injury or death!
The Series 8800 and 8900 come from the factory ready
to be piped to the gas supply. If for any reason the
boiler/water heater is not for the type of gas available
at the installation site, call the nearest RBI
representative to resolve the problem.
NOTE: A minimum gas supply presssure of 6 in,
152 mm W.C. natural or 11 in, 279 mm W.C. propane
and maximum 14 in, 356 mm W.C. natural or
propane, must be available at the safety shutoff
valve inlet with the unit(s) operating.
Table 8 should be used to ensure that the gas supply
piping is sized properly. If more than one appliance is
supplied by the same supply pipe, the piping must be
sized based on the maximum possible demand. Do not
neglect the pressure drop due to pipe fittings. Table 8
should be used in conjunction with Table 9 to ensure
that the gas supply piping has the capacity to meet the
demand.
Figure 12 depicts the proper way to connect the boiler/
water heater to the gas supply piping. The manual shut-
off valve MUST be installed in the supply piping. It
should be installed 5 ft, 1.5 m above the floor where
required by local codes. Provide a sediment trap at the
bottom of the vertical section of the gas supply pipe
upstream of the gas controls.
Table 8 - Gas Pipe Capacity
Maximum pipe capacity in ft
at a pressure of 0.5 psig or less and a 0.3" W.C. pressure drop.
Nominal
Iron Pipe
10
20
Size, (in)
1"
520
350
1 1/4"
1050
730
1 1/2"
1600
1100
2"
3050
2100
1650
2 1/2"
4800
3300
2700
3"
8500
5900
4700
4"
17,500
12,000
9700
Note: Multiply the gas volume by 0.62 for propane flow capacity in ft
Multiply the propane flow capacity by 2500 Btu/ft3 to determine the propane Btu/hr
capacity for a given pipe size and length.
3
/hr based on 0.60 specific gravity gas
Pipe length in feet
30
40
50
60
80
3
Maximum gas volume of pipe, (ft
/hr)
285
245
215
195
170
590
500
440
400
350
890
760
670
610
530
1450
1270
1150
990
2300
2000
1850
1600
4100
3600
3250
2800
8300
7400
6800
5800
3
/hr.
A ground joint union should be installed between the
boiler gas controls and the supply piping. Each of these
items are needed to ensure long life and ease of
servicing. Always use a pipe sealant that is suitable for
use with LP gas.
Table 9 - Equivalent Pipe Length Chart
Nominal
Iron Pipe
Size, (in)
1 1/4"
1 1/2"
2 1/2"
Notes: 1. For flow through branch.
CAUTION: Always use a square jawed wrench on the
gas valve body when making gas connections to it.
Never over-tighten the piping entering the gas valve
body or gas valve failure may result!
Figure 12 - Gas Supply Piping
When applicable, provisions for vent, bleed and gas
relief lines must be made in accordance with the latest
revision of ANSI Z223.1/NFPA 54.
Safe lighting and other performance criteria were met
with the gas manifold and control assembly provided on
the boiler. All gas connections MUST be leak tested
before putting the boiler into operation.
WARNING: Never use an open flame to test for
100
150
gas leaks. Always use an approved leak
detection method. Failure to comply with this
150
120
warning can cause extensive property damage,
305
250
severe personal injury or death!
460
380
870
710
1400
1130
2500
2000
5100
4100
Type of pipe fitting
90°
Gate
1
Elbow
Tee
Valve
Equivalent of pipe length (ft)
1"
2.6
5.2
0.6
3.5
6.9
0.8
4.0
8.0
0.9
2"
5.2
10.3
1.2
6.2
12.3
1.4
3"
7.7
15.3
1.8
4"
7.7
15.3
1.8
2. For flow at full open.
Gas
2
2
Cock
1.5
1.9
2.3
3.0
3.7
4.5
4.5
RIOM-47

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents