Clearances To Combustibles (Ul And Ulc) - Heatilator ECO-ADV-WS22 Owner's Manual Installation And Operation

Wood burning stove
Hide thumbs Also See for ECO-ADV-WS22:
Table of Contents

Advertisement

B. Clearances to Combustibles (UL and ULC)
BACKWALL / SIDEWALL
A
B
C
D
CORNER INSTALLATION
E
F
E
F
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS: Inches & (Millimeters)
NOTE: All "A", "C" and "F" dimensions are to inside diameter of flue collar.
INSTALLATION: Full Vertical OR Horizontal with 2 foot (609mm) minimum vertical Off Stove Top
SINGLE WALL PIPE
DOUBLE WALL PIPE
INSTALLATION: 90
SINGLE WALL PIPE
DOUBLE WALL PIPE
INSTALLATION: ALCOVE
insulated connector pipe with UL103 HT** Listed factory-built Class "A" chimney, or a masonry
chimney. (Mobile Home must be equipped with a spark arrestor). Maximum depth of Alcove shall be
no more than 48 inches (1219mm) with a minimum height of 84 inches (2133mm) from floor to
bottom of ceiling and the referenced clearances.
**In Canada must comply with Standard CAN/ULC-S629-M87 for the 650
* SEE PIPE MANUFACTURERS CLEARANCES - NOT TESTED
WARNING! Risk of Fire!
• Comply with all minimum clearanes to combustibles
as specified.
• Failure to comply may cause house fire.
30
NOTE: Clearances may only be reduced by means
approved by the regulatory authority having jurisdiction
90° OFF TOP
UP & OUT CEILING
CLEARANCE
STOVE TO CEILING
CLEARANCE
A
B
10 (254) 8.25 (210) 21 (533)
9 (229)
7 (178) 19.5 (495)
o
ELBOW OFF TOP OF STOVE THROUGH BACKWALL
9.25 (235) 7.5 (191) 18 (457)
9.25 (235) 7.5 (191) 18 (457)
Six inch (6") (152mm) diameter listed Single Wall or Double Wall air
Heatilator • ECO-ADV-WS22 • 7057-128C • August 13, 2010
H
G
C
D
E
11 (279) 3.5 (89) 12.5 (318) 49 (1245)
9 (229)
3 (76)
8 (203) 3.5 (89) 12.5 (318) 49 (1245)
8 (203)
3 (76) 12 (305)
o
C Factory-built chimney.
NOTE: Service Space
In order to replace the tube channel assembly a clearance
of 19 inches (483mm) is required on the right side of stove
in order to remove the tubes with the stove in place.
If space is not available, the stove will have to be discon-
nected from the chimney to proceed with the tube replace-
ment.